12.24 External Compressor Switch (Optional PCB)

External compressor switch port can have two purpose of control as below:
Heat source ON/OFF function (Dip switch Pin 3 on PCB "OFF")
Heater ON/OFF function (Dip switch Pin 3 on PCB "ON")
Heat source ON/OFF function
Purpose:
Heat pump ON/OFF function is use to turn OFF the high power consumption device (Heat pump, & Heater) when
there is energy or electric current limitation. Other optional function still can be operate under heat pump and
heater OFF condition.
Control Detail:
This External Compressor Switch is possible to connect to Optional PCB only.
Once the remocon select External Compressor Switch connection "YES", & Dip Switch on PCB "OFF"
This heat pump ON/OFF function will activate
The ON/OFF signal of this External Compressor Switch is same as External Switch.
When the External Compressor Switch is ON:
Heat pump system operate normally
o
When the External Compressor Switch is OFF:
Heat pump, Indoor water pump & Heater ( Booster heater & Backup Heater ) need to turn OFF
o
Solar, Boiler and zone control can be operate follow normal control condition.
o
* pump delay OFF also included in this control
(There is NO pop up screen like External Switch when this External Compressor Switch is OFF.)
Heater ON/OFF function
Purpose:
Heater ON/OFF function is use to turn OFF the heater (backup heater & booster heater) when there is energy or
electric current limitation. Heat pump and other optional function still can operate.
Control detail:
This External Compressor Switch is possible to connect to Optional PCB only.
Once the remocon select External Compressor Switch connection "YES", & Dip Switch on PCB "ON"
This heater ON/OFF function will activate
When the External Compressor Switch is ON:
Heat pump and heater operate normally
o
When the External Compressor Switch is OFF:
Backup heater and booster heater cannot operate even heater request is ON.
o
Heat pump and option function (Solar, Boiler and zone control) can be operate follow normal control
o
condition.
(There is NO pop up screen like External Switch when this External Compressor Switch is OFF.)

12.25 Heat/Cool Switch (Optional PCB)

Purpose:
User can switch the running mode from heat to cool or cool to heat through external installed Heat/Cool switch.
This kind of heat / cool switch may built in inside the field supply room remocon as well.
Control contents:
Heat/Cool Switch can only be set when Cool Function is "enable" at custom menu setting, & Extension PCB
select "YES" & Zone 1 not set "Pool" condition.
This heat/cool switch control will be activate only when installer set the Heat/Cool Switch "USE" through remocon.
Once the Heat/Cool Switch Set "USE", remocon will check indoor send Signal to judge the option of mode select.
When Heat/Cool Switch Contact Open : Remocon only can select Heat Mode, or Heat + Tank Mode, or Tank
o
Mode
When Heat/Cool Switch Contact Close : Remocon only can select Cool Mode, or Cool + Tank Mode, or Tank
o
Mode