Panasonic WH-ADC0309H3E Service Manual page 76

Air-to-water hydromodule + tank
Table of Contents

Advertisement

10 Demand signal cable shall be (2 x min 0.3 mm
sheathed cable.
11 SG signal cable shall be (3 x min 0.3 mm
cable.
12 Heat/Cool switch cable shall be (2 x min 0.3 mm
sheathed cable.
13 External compressor switch cable shall be (2 x min 0.3 mm
rubber-sheathed cable.
Bind all
optional cables
with these
bands
Bind optional
cables with
these bands
Power Supply 2
RCCB/ELCB
Power Supply 1
RCCB/ELCB
Indoor
terminal for
connecting
cables
Bind all optional
cables with these
bands
How to guide the optional cables and power supply cord
(view without internal wiring)
Terminal screw on PCB
M3
M4
11.3.2.2
Connecting Cables Length
When connecting cables between Tank Unit and external devices, the length of the said cables must not exceed the
maximum length as shown in the table.
Optional
PCB
Bind optional
cables with
these bands
Holder (Clamper)
Maximum tightening torque cN•m {kgf•cm}
50 {5.1}
120 {12.24}
External device
Two-way valve
Mixing valve
Room thermostat
Extra pump
Solar pump
Pool pump
Pump
Boiler contact
External control
Room sensor
Outdoor air sensor
Buffer tank sensor
Pool water sensor
Solar sensor
Water sensor
Demand signal
SG signal
Heat/Cool switch
External compressor switch
2
), double insulation layer of PVC-sheathed or rubber-
2
), double insulation layer of PVC-sheathed or rubber-sheathed
2
), double insulation layer of PVC-sheathed or rubber-
2
), double insulation layer of PVC-sheathed or
Optional cables:
2-way valve cable
Extra pump cable
Boiler contact cable
Optional cables:
External control cable
Outdoor air sensor cable
Remote controller cable
Room sensor zone 1 cable
Room sensor zone 2 cable
Buffer tank sensor cable
Pool sensor cable
Water sensor zone 1 cable
Water sensor zone 2 cable
Demand signal cable
Solar sensor cable
SG signal cable
Heat/Cool switch cable
External Compressor switch cable
Maximum cables length (m)
50
50
50
50
50
50
50
50
50
30
30
30
30
30
30
50
50
50
50
76
Power Supply 1 cord
Power Supply 2 cord
Indoor Unit/Outdoor
Unit Connecting cable
Optional cables:
Pump zone 1 cable
Pump zone 2 cable
Solar pump cable
from Optional
Pool pump cable
PCB
Room thermostat zone 1 cable
Room thermostat zone 2 cable
Mixing valve zone 1 cable
Mixing valve zone 2 cable
from Optional PCB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-ud07he5-1Wh-ud09he5-1Wh-ud03he5-1Wh-ud05he5-1

Table of Contents