Protection Control For Heating Operation - Panasonic WH-ADC0309H3E Service Manual

Air-to-water hydromodule + tank
Table of Contents

Advertisement

14.2

Protection Control for Heating Operation

14.2.1 Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid
compressor overloading.
14.2.2 Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor
stop.
Deice judging condition
Outdoor Unit Deice Control
10
5
0
-5
-10
-15
-20
-25
-30
-30
Deice operation time diagram
a. Deice mode 1 control:
Compressor
Four way valve
ID pump
OD fan
Expansion valve
-20
-10
Outdoor Temperature (°C)
Free
1
2
ON
ON
Free
Free
When Heating Time > 35 minutes
and Pipe Temperature below this
line for continuous 3 minutes
0
10
3
5
4
OFF
ON
OFF
max 9 minutes 30 seconds
deice 1
131
Deice start depends:
1. Outdoor air sensor temp.
2. Outdoor pipe sensor temp.
3. Heating accumulation time
20
30
8
6
7
Free
9
ON
ON
Free