Parallel Mode
Parallel mode allows heat pump and boiler ON at the same time. Boiler operates as an additional heating
o
capacity when low heat pump capacity at low ambient condition.
Control detail:
During operation ON at Heat mode or Tank mode or Heat + Tank mode
Boiler signal turns ON when:
o
Outdoor ambient < Outdoor Ambient Set AND
Boiler prohibit flag = 0
Boiler signal turns OFF when:
o
Outdoor ambient > Outdoor Ambient Set + [2°C] OR
Boiler prohibit flag = 1
Advance Parallel Mode
Advance parallel mode allow heat pump to operate and turn ON boiler only when ambient and temperature
o
condition is fulfilled.
Remote control setting value:
1
Outdoor Ambient Set = (Range : -15°C ~ 15°C)
2
Selection of boiler connection direction. (Heat only, DHW only, Heat & DHW)
3
Setting data under Heat Direction
Start Temperature
o
Start Delay Timer
o
Stop Temperature
o
Stop Delay Timer
o
4
Setting data under DHW Direction
Delay Timer
o
Control detail:
During operation ON at Heat Mode
Boiler signal turns ON when
o
Outdoor ambient < Outdoor Ambient Set AND
Buffer tank temperature < Target Buffer Tank Temperature + [START_TEMP] for [START_TIMER]
AND
Heat pump operate at room side AND
Connection of Boiler to Heating Select "YES" From installer menu AND
Buffer Tank connection select "YES" AND
Boiler prohibit flag = 0
Boiler signal turns OFF when
o
Outdoor ambient > Outdoor Ambient Set + [-2°C] OR
Buffer Tank temperature > Target Buffer Tank temperature + [STOP_TEMP] for [STOP_TIMER] OR
Heat pump not at room side. OR]
Boiler prohibit flag = 1
During operation ON at Tank Mode
Boiler signal turns ON when
o
Outdoor ambient < Outdoor Ambient Set AND
Heat pump operate at tank side for continuous | DELAY_TIMER | AND
Connection of Boiler to DWH Tank select "YES" from installer menu. AND
Boiler prohibit flag = 0
Boiler signal turns OFF when
o
Outdoor ambient > Outdoor Ambient Set + [2°C] OR
Heat pump not operates at tank side. OR
Boiler prohibit flag = 1
Boiler prohibit flag control
Purpose:
For product safety. Boiler signal is OFF when water temperature is too high.
o
| START_TEMP |
| START_TIMER |
| STOP_TEMP |
| STOP_TIMER |
| DELAY_TIMER |
117