Panasonic WH-ADC0309H3E Service Manual page 75

Air-to-water hydromodule + tank
Table of Contents

Advertisement

11.3.2 How to fix cable
11.3.2.1
Connecting with external device (optional)
All connections shall follow to the local national wiring standard.
It is strongly recommended to use manufacturer-recommended parts and accessories for installation.
For connection to main PCB
1
Two-way valve shall be spring and electronic type, refer to "Field Supply Accessories" table for details. Valve
cable shall be (3 x min 1.5 mm
sheathed cable.
* note: - Two-way Valve shall be CE marking compliance component.
- Maximum load for the valve is 9.8VA.
2
Room thermostat cable must be (4 or 3 x min 0.5 mm
similarly double insulation sheathed cable.
3
Extra pump cable shall be (2 x min 1.5 mm
4
Boiler contact cable shall be (2 x min 0.5 mm
5
External control shall be connected to 1-pole switch with min 3.0 mm contact gap. Its cable must be (2 x min
2
0.5 mm
), double insulation layer of PVC-sheathed or rubber-sheathed cable.
* note: - Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
6
Room sensor zone 1 cable shall be (2 x min 0.3 mm
sheathed.
7
Outdoor air sensor cable shall be (2 x min 0.3 mm
sheathed.
Main PCB
Power Supply 2
RCCB/ELCB
Power Supply 1
RCCB/ELCB
Indoor
terminal for
connecting
cables
Holder (Clamper)
How to guide the optional cables and power supply cord
(view without internal wiring)
For connection to Optional PCB
1
By connecting Optional PCB, 2 Zone temperature control can be achieved. Please connect mixing valves,
water pumps and thermistors in zone 1 and zone 2 to each terminals in Optional PCB.
Temperature of each zone can be controlled independently by remote controller.
2
Pump zone 1 and zone 2 cable shall be (2 x min 1.5 mm
3
Solar pump cable shall be (2 x min 1.5 mm
4
Pool pump cable shall be (2 x min 1.5 mm
5
Room thermostat zone 1 and zone 2 cable shall be (4 x min 0.5 mm
heavier.
6
Mixing valve zone 1 and zone 2 cable shall be (3 x min 1.5 mm
heavier.
7
Room sensor zone 1 and zone 2 cable shall be (2 x min 0.3 mm
strength of minimum 30V) of PVC-sheathed or rubber-sheathed cable.
8
Buffer tank sensor, pool water sensor and solar sensor cable shall be (2 x min 0.3 mm
layer (with insulation strength of minimum 30V) of PVC-sheathed or rubber-sheathed cable.
9
Water sensor zone 1 and zone 2 cable shall be (2 x min 0.3 mm
or rubber-sheathed cable.
2
), of type designation 60245 IEC 57 or heavier, or similarly double insulation
2
2
), of type designation 60245 IEC 57 or heavier.
2
), of type designation 60245 IEC 57 or heavier.
2
) double insulation layer of PVC-sheathed or rubber-
2
) double insulation layer of PVC-sheathed or rubber-
Bind optional
cables with
these bands
Bind optional
cables with
these bands
2
), of type designation 60245 IEC 57 or heavier.
2
), of type designation 60245 IEC 57 or heavier.
75
), of type designation 60245 IEC 57 or heavier cord, or
.
rms
Optional cables:
2-way valve
cable
Room thermostat zone
1 cable
Extra pump cable
Boiler contact cable
2
), of type designation 60245 IEC 57 or heavier.
2
), of type designation 60245 IEC 57 or
2
), of type designation 60245 IEC 57 or
2
), double insulation layer (with insulation
2
), double insulation layer of PVC-sheathed
Optional cables:
External control
cable
Room sensor
zone 1
Outdoor air sensor
cable
Remote controller
cable
Power Supply 1 cord
Power Supply 2 cord
Indoor Unit/Outdoor Unit Connecting cable
2
), double insulation