Panasonic WH-ADC0309H3E Service Manual page 179

Air-to-water hydromodule + tank
Table of Contents

Advertisement

17.5.30 Input Over Current Detection (F16)
Malfunction Decision Conditions:
During operation of cooling and heating, when outdoor current above 14.8 A (UD03HE5-1, UD05HE5-1), 27.9 A
(UD07HE5-1, UD09HE5-1) is detected by the current transformer (CT) in the outdoor unit PCB.
Malfunction Caused:
1
Excessive refrigerant.
2
Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 3 times in 20 minutes.
Troubleshooting:
Get restarted and measure
the AC current from the
outdoor LIVE terminal.
Is the measured AC current
over 14.8 A (UD03HE5-1,
UD05HE5-1) and 27.9 A
(UD07HE5-1, UD09HE5-1)?
Check refrigerant amount.
Excess refrigerant?
No
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
No
Replace the outdoor unit
PCB (main).
Yes
Reclaim and recharge with
correct amount of refrigerant.
Replace the outdoor unit
PCB (main).
179

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-ud07he5-1Wh-ud09he5-1Wh-ud03he5-1Wh-ud05he5-1