Panasonic WH-ADC0309H3E Service Manual page 171

Air-to-water hydromodule + tank
Table of Contents

Advertisement

17.5.22 Indoor/Outdoor Abnormal Communication (H90)
Malfunction Decision Conditions:
During operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is
checked whether it is normal.
Malfunction Caused:
1
Faulty outdoor unit PCB (main).
2
Faulty indoor unit PCB (main).
3
Indoor-outdoor signal transmission error due to wrong wiring.
4
Indoor-outdoor signal transmission error due to breaking of wire in the connection wires between the indoor
and outdoor units.
5
Indoor-outdoor signal transmission error due to disturbed power supply waveform.
Abnormality Judgment:
Continue for 1 minute after operation.
Troubleshooting:
Turn OFF the power and disconnect
terminal 3 wire. Turn ON the power
and measure Vdc between terminal
Turn OFF the power and reconnect
terminal 3 wire. Turn ON the power
Check the indoor-outdoor
units connection wires.
Is there any wiring error?
No
2 & 3 from the outdoor unit.
Is the Vdc fluctuate
between 45-60 Vdc?
Yes
and again measure Vdc between
terminal 2 & 3 from outdoor unit.
Is the Vdc fluctuate
between 15-60 Vdc?
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Yes
Correct the indoor-outdoor
units connection wires.
No
Replace the outdoor unit
No
Replace the indoor unit
171
PCB (main).
PCB (main).

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-ud07he5-1Wh-ud09he5-1Wh-ud03he5-1Wh-ud05he5-1

Table of Contents