Mode Settings - Panasonic U-10MF1E8 Service Manual

3-way system
Hide thumbs Also See for U-10MF1E8:
Table of Contents

Advertisement

6. Mode Settings

■ Setting mode 1
<Operating procedure>
Press and hold the
(VENTILATION) button simultaneously for 4
seconds or longer.
Use the temperature setting
buttons to change the item code. The item codes
and setting data are shown in the table below.
Use the timer time
the setting data.
To confirm the changed setting data, press the
button.
(At this time, "
lit.)
During this mode, "
The outdoor unit address display section displays
"ALL," the item code number (DN value in the
table), and the setting data (8 digits).
3
(The setting data is displayed in 8 digits. The
display changes between the first 4 digits (Fig.
and the last 4 digits (Fig.
digits are displayed, the bottom dot of the colon is
lit.)
To exit the setting mode, press the
button.
DN
Snowfall sensor usage
Outdoor unit fan Quiet
mode
Energy saving mode
Energy saving operation
plug
Demand 1 current
Demand 2 current
High static pressure mode
(CHECK) button and
and
and
buttons to change
" stops blinking and remains
" is displayed, blinking.
B
). When the first 4
(CHECK)
Parameter
0 = Sensor input not present. Control is performed.
1 = Sensor input present. Control is performed.
2 = Sensor input not present. Control is not performed.
3 = Sensor input present. Control is not performed.
0 = Disabled
2 = Quiet mode 2
4 = Quiet mode 4
0 = None
1 = Discharge temp. control only (Mode 3)
2 = Demand only (Mode 2)
3 = Discharge temp. control + Demand (Mode 1)
0 = Independent
1 = All indoor units linked
0 = 0% 1 = 40 ... 4 = 70 7 = 100 8 = 120
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)
0 = 0% 1 = 40 ... 4 = 70 7 = 100 8 = 120
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)
0 = Disabled
* Charge when the external static pressure is increased to over 30 Pa.
Outdoor Unit Maintenance Remote Controller
A
Display of fi rst 4 digits
5
1
B
Display of last 4 digits
A
)
5
1
A
B
and
(Example shows display of 0000 0001.)
Description
1 = Quiet mode 1
3 = Quiet mode 3
6 = High static pressure mode
3 - 12
3-WAY SYSTEM
3
3
are displayed alternately.
2
2

Advertisement