1-12. Optional Distribution Joint Kits

See the installation instructions packaged with the distribution joint kit for the installation procedure.
Table 11
Model name
1. CZ-P160BK2
* In case the total capacity of indoor units connected after distribution exceeds the capacity of the outdoor unit, select the distribution
tubing size for the capacity of the outdoor unit.
■ Tubing size (with thermal insulation)
1. CZ-P160BK2
Use: Total capacity of indoor units after distribution joint is 22.4 kW or less.*
Example:
A
Distribution
Insulation
Joint
Table 12 : Size of connection point on each part (Shown are inside diameters of tubing)
Size
Part A
mm
ø19.05
* In case the total capacity of indoor units connected after distribution exceeds the capacity of the outdoor unit, select the distribution
tubing size for the capacity of the outdoor unit.
Cooling capacity
Remarks
after distribution
22.4 kW or less *
For indoor unit
Gas tube
110
97
C
B
B
A
B
C
Part B
Part C
Part D
ø15.88
ø12.7
ø9.52
Liquid tube
D
Insulation
Part E
ø6.35
15
110
97
C
D E
C
Distribution
C
Joint
D
E
Unit: mm