Storage Tank Charging; Charging Control Via The Storage Tank Temperature - Siemens Synco 700 Basic Documentation

Modular heating controller rmh760b including extension modules rmz782b, rmz783b, rmz787 and rmz789
Hide thumbs Also See for Synco 700:
Table of Contents

Advertisement

Inputs / setpoints
(display)
Settings
Storage tank sensor at
the top
Starting storage tank
charging
Ending storage tank
charging
156/238
Building Technologies
HVAC Products
The setpoint currently active for storage tank charging appears on the Main menu and
on the info page.
Main menu > DHW > Inputs/setpoints
Operating line
Storage tank temp setpoint
For detailed information about the generation of the storage tank temperature setpoint,
refer to subsection 10.4.1 "Charging control via the storage tank temperature".
10.4

Storage tank charging

Storage tank charging (DHW 0...DHW 5) and thus primary control (refer to section 10.7
"Primary control") can be started and / or terminated via different functions:
• Storage tank temperature (according to the current operating mode)
• Maximum charging time
• Forced charging
The following settings enable the functions to be activated or matched to specific
needs:
Main menu > Settings > DHW > DHW
Operating line
Switching differential
Setback DHW setpoint bottom
Charging time max
Forced charging

10.4.1 Charging control via the storage tank temperature

Normally, storage tank charging is controlled via the storage tank temperature.
Charging is started as soon as the storage tank temperature drops below the switch-on
point; it ends when the storage tank temperature setpoint (TStTaSetpt) is reached.
Charging can also be activated via forced charging and aborted when the maximum
charging time is reached (refer to subsections 10.4.2 "Forced charging" and 10.4.3
"Maximum charging time").
If there is no storage tank sensor at the bottom, charging control is effected via one
sensor only.
To start storage tank charging, the storage tank temperature must have dropped below
the storage tank temperature setpoint (TStTaSetpt) by the amount of the (adjustable)
switching differential (SDDhw).
Charging is ended as soon as the storage tank temperature has reached the setpoint.
Modular Heating Controller RMH760B
10 DHW heating
Range
5...140 °C
Range
1...20 K
0...20 K
---- / 5...250 min
Never /
With 1st change to normal /
With every change to
normal
ON
TStTaTop
T
OFF
Factory setting
Factory setting
5 K
5 K
----
Never
SDDhw
T
T
=
TStTa
ON
OFF
TStTaSetpt
CE1P3133en
05.02.2007