Limitation Of The Return Temperature - Siemens Synco 700 Basic Documentation

Modular heating controller rmh760b including extension modules rmz782b, rmz783b, rmz787 and rmz789
Hide thumbs Also See for Synco 700:
Table of Contents

Advertisement

Settings
Room limitation increase
Room lim switching differ-
ential
Building Technologies
HVAC Products
TR
on
Pump
off
TR
TRSD
on
off
TRw
t
Time
Δ TR
Temperature differential for switching the heating circuit off
TR
Room temperature
TRSD
Temperature differential for switching the heating circuit on
TRw
Room temperature setpoint
TRx
Actual value of room temperature
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Heating circuit 1 (or 2 or 3 ) > Limitations
Operating line
Room limitation increase
Room lim switching differential
The room limitation increase is used to set the temperature differential for switching off
the heating circuit.
The room limitation switching differential is used to set the temperature differential for
switching on the heating circuit.
9.8.2

Limitation of the return temperature

The heating circuit's mixing valve can be used to provide maximum limitation of the
return temperature. Minimum limitation is not supported. By contrast, the boiler sup-
ports minimum limitation with certain restrictions for all consumers. For more detailed
information, refer to subsection 9.8.3 "Minimum limitation of the return temperature".
B1
M1
B7
Y1
Main controller
B1
Flow temperature sensor
B7
Return temperature sensor
M1
Heating circuit pump
Y1
Heating circuit mixing valve
Modular Heating Controller RMH760B
9 Heating circuit control
TRx
TRw + TR
TRw + TR - TRSD
TRw
t
TR
Range
---- / 0.5...5.0 K
0.2...5.0 K
Y1
B1
M1
B7
Primary controller
Factory setting
----
0.2 K
135/238
CE1P3133en
05.02.2007