Siemens Synco 700 Basic Documentation page 122

Modular heating controller rmh760b including extension modules rmz782b, rmz783b, rmz787 and rmz789
Hide thumbs Also See for Synco 700:
Table of Contents

Advertisement

Impact on the
Comfort setpoint
Note
Impact on the
Precomfort setpoint
122/238
Building Technologies
HVAC Products
The figure at the top shows the difference between the remote setpoint adjuster and the
adjusted Comfort setpoint for heating. This difference impacts the other setpoints very
differently. This is shown in the figure at the bottom.
0 K
Setpt C H Cmf
z.B. / e.g.:
Setpt C Prt
32 °C
Setpt C Eco
28 °C
25 °C
Setpt C PreC
23 °C
Setpt C Cmf
Setpt H Cmf
21 °C
Setpt H PreC
19 °C
16 °C
Setpt H Eco
Setpt H Prt
12 °C
C
Cooling
Cmf
Comfort
Eco
Economy
H
Heating
The current Comfort setpoint
juster.
Although the Comfort setpoint is predefined by the remote setpoint adjuster, a fixed
Comfort setpoint for heating need be entered on Main menu > Heating circuit 1 (or 2 or 3 ) >
Room setpoints . From the difference between the fixed Comfort setpoint "Heating" and
the adjustment made with the remote setpoint adjuster, the current Comfort setpoint
"Cooling" can be calculated:
Comfort setpoint "Cooling" + (remote setpoint minus Comfort setpoint "Heating")
The RMH760B has no Comfort setpoint "Cooling". The impact on the Comfort setpoint
"Cooling" as described above is only possible in connection with a room control combina-
tion. For more detailed information, refer to subsection 9.10.3 "Room control combina-
tion".
The setpoint shift is limited by the setpoints for Protection mode. Also refer to the graph
above.
The Precomfort setpoints
Hence, the current Precomfort setpoint "Heating" is calculated as follows:
Precomfort setpoint "Heating" + ("Remote setpoint" minus Comfort setpoint "Heating")
And the current Precomfort setpoint "Cooling" is calculated as follows:
Precomfort setpoint "Cooling" + ("Remote setpoint" minus Comfort setpoint "Heating")
The note above in paragraph "Comfort
setpoint.
Modular Heating Controller RMH760B
9 Heating circuit control
+10 K
0 K
PreC Precomfort
Prt
Protection
Setpt Setpoint
is the setpoint adjusted with the remote setpoint ad-
are shifted also:
" also applies analogously to the Precomfort
0 K
-10 K
CE1P3133en
05.02.2007