Maximum limitation of
the return temperature
Maximum limitation in
space heating mode
Special cases:
Maximum limitation in
DHW heating mode
106/238
Building Technologies
HVAC Products
If the return temperature exceeds the limit value, the primary controller's flow tempera-
ture setpoint will be lowered. If the return temperature drops below the limit value,
reduction of the flow temperature setpoint will be negated again. Limitation is provided
in the form of an I-controller whose integral action time can be adjusted.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Main controller > Mixing circuit controller
Main menu > Settings > Primary controller > Mixing circuit controller
Operating line
[Tn] return temp limitation max
Maximum limitation will be effective when only heating and ventilation are active at the
respective primary controller. It will be deactivated as soon as DHW heating is started.
With this limitation, the return temperature limit value changes depending on the out-
side temperature. Maximum limitation will be activated when a valid value is set for at
least one maximum return temperature setpoint.
[Curvepoint 1]
TRtLim
Return temperature
[Curvepoint 1]
Outside temperature
TRtLim
Limit value of return temperature limitation
TOeff
Composite (effectively acting) outside temperature
Curvepoint 1
Maximum return temperature limit value, active at low outside temperatures
Curvepoint 2
Minimum return temperature limit value, active at high outside temperatures
Setting
Return temperature curvepoint 1 =
return temperature curvepoint 2
Outside temperature curvepoint 1 =
outside temperature curvepoint 2
Return temperature curvepoint 1 = ----
Return temperature curvepoint 2 = ----
Return temperature curvepoint 1 and
return temperature curvepoint 2 = ----
This limitation is effective when DHW heating is active at the primary controller. In that
case, maximum limitation in space heating mode will be deactivated.
Maximum limitation in DHW heating mode is constant, that is, independent of the
outside temperature.
The limitation can be overridden by maximum limitation in DHW heating mode with the
legionella function activated. For more detailed information, refer to the next section.
Modular Heating Controller RMH760B
8 Main controller and primary controller
Area
0...60 min
[Curvepoint 2]
Return temperature
TOeff
[Curvepoint 2]
Outside temperature
Effect
Constant limitation of the return tem-
perature. Outside temperature is irrele-
vant
Limit value of return temperature
changes abruptly at the curvepoints
Constant return temperature limitation
with curvepoint 2 as the maximum return
temperature setpoint. Outside tempera-
ture is irrelevant
Constant return temperature limitation
with curvepoint 1 as the maximum return
temperature setpoint. Outside tempera-
ture is irrelevant
In space heating mode, limitation of the
return temperature is deactivated
Factory setting
30 min
CE1P3133en
05.02.2007