Mixing Valve Control; Pump Control; Plant Operation - Siemens Synco 700 Basic Documentation

Modular heating controller rmh760b including extension modules rmz782b, rmz783b, rmz787 and rmz789
Hide thumbs Also See for Synco 700:
Table of Contents

Advertisement

Fault setting primary
controller
Fault setting main
controller

Plant operation

Building Technologies
HVAC Products
The flow or return temperature sensor of primary controller type 2 can be used for
display purposes.
By configuring the outputs, it is determined whether primary controller type 1 or 2 is used.
Without configuration of a mixing valve, primary controller type 2 is automatically used.
But a flow temperature increase can also be defined with primary controller type 2 to
compensate for temperature losses in the case of long pipes. For more detailed informa-
tion about flow temperature increase, refer to section 8.7 "Setpoint increase".
8.3.1

Mixing valve control

For control of the mixing valve, a 3-position or DC 0...10 V actuator can be used. The
selection is made by configuring the relevant output.
8.3.2

Pump control

Pump control offers a number of monitoring choices independent of whether the pump
is a single pump or twin pump.
For more detailed information about pump control and twin pumps, refer to section 5.8
"Pump control and twin pumps".
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Main controller > Fault settings > Overload pump
Operating line
Fault acknowledgement
Fault acknowledgement B
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Primary controller > Fault settings > Overload pump
Operating line
Fault acknowledgement
Fault acknowledgement B
8.4
Plant operation
Plant operation indicates whether the primary controller is switched on and whether the
pump is running.
Main menu > Main controller > Plant operation
Main menu > Primary controller > Plant operation
Operating line
Preselection
Setp preselection manual**
State
Cause
Modular Heating Controller RMH760B
8 Main controller and primary controller
Range
None / Acknowledge /
Acknowledge and reset
None / Acknowledge /
Acknowledge and reset
Range
None / Acknowledge /
Acknowledge and reset
None / Acknowledge /
Acknowledge and reset
Range
Auto / Off*
---- / 8...140 °C
Off / On
Commissioning /
Request /
Frost protection for con-
sumer /
Frost protection for the
flow /
Factory setting
Acknowledge
and reset
Acknowledge
and reset
Factory setting
Acknowledge
and reset
Acknowledge
and reset
Factory setting
Auto
----
99/238
CE1P3133en
05.02.2007