Device Information; Leaving The Password Level; Marking An Intervention - Siemens Synco 700 Basic Documentation

Modular heating controller rmh760b including extension modules rmz782b, rmz783b, rmz787 and rmz789
Hide thumbs Also See for Synco 700:
Table of Contents

Advertisement

Display values
Marking
Resetting the
marking
38/238
Building Technologies
HVAC Products
3.7

Device information

The Device information menu provides information about the controller, shows the soft-
ware version, etc.
Main menu > Device information > Controller
Operating line
Plant type
Plant type adapted
File name
Device type
Software version
Hardware version
Main menu > Device information > Position 1...4
Operating line
Extension module
Software version
Hardware version
3.8

Leaving the password level

On completion of commissioning, select the user level (access level for the plant opera-
tor). Proceed as follows:
After completing commissioning, you reach the "Main menu" again.
1.
2.
Press simultaneously the OK knob and the ESC button.
The Access levels menu appears.
3.
4.
Select the user level by turning the OK knob.
Confirm the selection by pressing the OK knob.
5.
3.9

Marking an intervention

If the internal standard application has been adapted or if, subsequently, the "Extra
configuration" menu has been accessed, an asterisk (*) appears in front of the plant's
type reference.
The asterisk denotes that the plant type has been complemented by extra functions.
The asterisk is set automatically when leaving the „Extra configuration" menu, even if
nothing has been changed. In addition, on the Device information menu, Yes will be set
on operating line Plant type adapted.
When, on the Basic configuration menu, the former or a new standard application is
loaded for the plant type, the asterisk disappears and No will appear on operating line
Plant type adapted. A new configuration is made based on the selected application.
Modular Heating Controller RMH760B
3 Commissioning
Adjustable values / display / remarks
Display of plant type
Display of intervention in the programmed
application (yes, no)
Has a function only in connection with
ACS7... Display of file name of the applica-
tion currently loaded.
Can be edited under Settings > Texts > File
name.
RMH760B-1...RMH760B-5
Display of software version
Display of hardware version
Adjustable values / display / remarks
Display of the module's type reference
Display of software version
Display of hardware version
CE1P3133en
05.02.2007