Slot UI Test
Figure 41 — Slot UI Test
To execute the "Slot UI Test" select the "Start Test" button. It which will request the operator to push each individual
slot eject button and observe the LED behavior. The LED will blink three times green then three times amber. Note that
when the RDX 8000 is in the slot UI test mode any inserted cartridge will not be ejected by the associated button push
during the test. Once all eight positions have been verified confirm completion of a successful test by selecting "Test
Passed" button which will create a "Slot UI Test passed" status.
Display Test
Figure 42 — Display Test
To execute the "Display Test" select the "Start Test" button. The local operator will then be asked to push the OCP
navigation button and observe the display. Each navigation button push will step the unit through a different display
action. The first four steps will change the display backlight from white, to red, to green, to blue verifying proper opera-
tion of the RGB backlight. The next two steps will first clear all display pixels (the observer should see no dots) then set
all pixels black (the observer should see no missing black dots in the field).