System Blocking Settings - Salda Ptouch Service Manual

Remote control panel
Hide thumbs Also See for Ptouch:
Table of Contents

Advertisement

B11
Fire protection settings.
B12
Controller box heating settings.
CO2 reduction settings.
B13
4.3.1. System blocking settings
F1
F2
Number
Function
I1
Current setting indication.
Number
Function
Block automatic control:
Auto: automatic control is enabled;
F1
Block: automatic control is disabled.
Standby blocking mode:
Never: standby is allowed;
F2
Always: standby is not allowed;
Heating season: standby is prohibited during heating season;
Cooling season: standby is prohibited during cooling season.
Standby time limit per day (in minutes). Maximum allowed standby
F3
time per 12 h. Standby timer resets at 0:00 and 12:00.
EN
4
I1
F3
9