6. AIR TEMPERATURE PROTECTION SETTINGS
F1
F2
Number
Function
I1
Current setting indication.
Number
Function
Supply temperature low limit (in °C * 10). Protects from supplying
too cold air.
F1
Range: [0-200 °C] (0-20.0 °C)
Supply temperature high limit (in °C * 10). Protects from supplying
F2
too hot air.
Range: [200-600 °C] (20.0-60.0 °C)
Supply temperature limit timeout. If supplied air temperature
remains outside set limits for specified period, supply temperature
F3
limit alarm and its related action is executed.
Range: [0-1000 s]
Supply temperature limit alarm:
F4
Show warning;
Stop system.
EN
6
I1
F4
F3
11