Code
Description
c42
Operating direction
16.4 End position guiding
Operating direction increasing/increasing
− Value above limit (end position guiding) (c35): The actuator stem moves the valve to the
top end position if the input signal reaches the value entered in this code. Setting c35 =
100.0 % causes this function (end position guiding: valve open) with a retracting actuator
stem to be deactivated.
− Value below limit (end position guiding) (c36): The actuator stem moves the valve to the
bottom end position if the input signal reaches the value entered in this code. Setting c36
= 0.0 % causes this function (end position guiding: valve closed) with an extending actu-
ator stem to be deactivated.
Direction of action: increasing/decreasing
− Value above limit (end position guiding) (c35): The actuator stem moves the valve to the
bottom end position if the input signal reaches the value entered in this code. Setting c35
= 100.0 % causes this function (end position guiding: valve open) with a retracting actua-
tor stem to be deactivated.
− Value below limit (end position guiding) (c36): The actuator stem moves the valve to the
top end position if the input signal reaches the value entered in this code. Setting c36 =
0.0 % causes this function (end position guiding: valve closed) with an extending actuator
stem to be deactivated.
Code
Description
c35
Value above limit (end position guiding)
c36
Value below limit (end position guiding)
The actuator stem moves to the end positions earlier if the end position guiding function is
active.
EB 8331-4 EN
Annex A (configuration instructions)
Default
Adjustment range
>>
>> (increasing/increasing)
<> (increasing/decreasing)
Default
Adjustment range
97.0 %
50.0 to 100.0 %
1.0 %
0.0 to 49.9 %
16-5