R/T3000 INT rear panel

Item
Description
UPS option card
1
USB communications port
2
Serial communications port
3
Ground bonding screw
4
Load segment 1 and 2 (one IEC-320-C19 receptacle)
5
Load segment 1 (three IEC-320-C13 receptacles)
6
Load segment 2 (three IEC-320-C13 receptacles)
7
Cord retention clip attachment location
8
Cord retention clip attachment location
9
Cord retention clip attachment location
10
Ground bonding screw
11

REPO port

12
Input power receptacle (IEC-320-C20) for country-specific plug
13
attachment
REPO port
The UPS includes an isolated REPO port. When properly wired, the REPO feature enables the power at
the UPS output receptacles to be switched off from a remote location. To use this feature, the REPO port
must be connected to a remote, normally-open switch (not supplied). The REPO switch is used in
conjunction with a main disconnect device that removes the AC source from the input of the UPS. When
the switch is closed:
The REPO feature immediately powers down protected devices and does not utilize the orderly
shutdown procedure initiated by power management software.
The REPO feature shuts down UPS units operating under either utility or battery power.
NOTE: If the UPS was operating on battery power when the remote switch was closed, no
power is available to the load devices until utility power is restored and the UPS has been
manually powered up.
Component identification 10