To replace the components, reverse the removal procedure.
IMPORTANT: Charge the batteries for at least 24 hours before supplying backup power to
devices. The batteries charge to:
• 80 percent of their capacity within 3 hours
• 100 percent of their capacity within 48 hours

Testing the new battery module

After installing the new battery module, press the Test/Alarm Reset button to initiate a self-test
a
self-test" on page 43).
IMPORTANT: The UPS does not execute a self-test until the batteries are 90 percent
charged.
IMPORTANT: Charge the batteries for at least 24 hours before supplying backup power to
devices. The batteries charge to:
• 80 percent of their capacity within 3 hours
• 100 percent of their capacity within 48 hours
If the installation has been successful, the Battery Fault LED is not illuminated. If the installation has not
been successful, the Battery Fault LED illuminates. If this occurs, repeat the UPS battery replacement
procedure (on page 47), and check the battery terminal connections. If the Battery Fault LED is still
illuminated, see "LED and audible alarm troubleshooting
For the location of buttons, see "UPS front panel controls (on page 7)."
For the location of LEDs, see "UPS front panel LED indicators (on page 7)."

Replacing the UPS

To remove the UPS:
Power down all attached load devices.
1.
Power down the UPS
2.
Switch the circuit breaker for any attached ERMs to the Off position.
3.
("Powering down the
UPS" on page 44).
("LED
troubleshooting" on page 54)."
("Initiating
Maintenance 48