6. Technical Specifications

6.2 HPE R/T3000 G4 HV NA/JP UPS and HPE R/T3000 G4 INTL UPS

Filter
Output Power @ 200V
Output Power @ 208V
Output Power @ 230V
AC Input power
l Rated input voltage
l Input voltage range
l input frequency range
Output on battery power
l Voltage
l Frequency
Battery
(sealed lead acid,
maintenance free)
l Standard
l Additional
modules possible
(up to 4 ERMs)
Environment
l Operating
temperature range
l Storage
temperature range
l  R elative humidity
l Noise level
(1) The high and low thresholds can be adjusted using UPS settings (up to 150-294V).
(2) Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).
(3) Adjustable to 200/208/220/230/240V, but must be set to the identical AC power source value.
When the UPS is used in the EU area, use an external circuit breaker in front of the line with rating 16A,
250V which is IEC/EN 60898-1 standard compliant.
When the UPS is used in the NA area, use an external circuit breaker in front of the line with rating 20A, 250V.
Caution: To reduce the risk of fire, only connect to a circuit provided with 30A maximum branch circuit overcurrent protection
in accordance with the National Electric Code, ANSI/NFPA 70.
Page 30
Transformer
AVR
Charger
HPE R/T3000 G4 HV NA/JP UPS
2490V
2241W
NA: 3000 VA
2700W
JP: 2490 VA
2241W
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
208/230V (-10% to +5%)
20 to 90% (without condensation)
< 45 dBA
Inverter
Battery
HPE R/T3000 G4 INTL UPS
Single phase 200-240V
160 to 294V
(1)
(3)
50/60 Hz ±0.1 Hz
6 x 12V
9 Ah
HPE R/T3000 G4 ERM
12 x 12V
9 Ah
(2 strings of x6)
0 to 40°C
-15 to +50°C
2490V
2241W
3000 VA
2700W
(2)
< 50 dBA
792519-001 Edition 2