Initiating A Self-Test; Silencing An Audible Alarm - HPE R/T3000 G2 User Manual

Table of Contents

Advertisement

Available settings Parameter
Wiring fault setting
NOTE: For high voltage UPSs, the Site Wiring Fault function is disabled by default, but can
be manually enabled.
To change the UPS configuration parameters:
Place the UPS in Configure mode (on page 41).
1.
The LEDs associated with the currently configured parameters illuminate. A flashing cursor indicates
where you are in the configuration process as you scroll through the available settings.
Press the On button to scroll through the options. Each time the On button is pressed, the audible
2.
alarm sounds.
If the On button is pressed and the UPS does not respond, the UPS is in Operate mode (on page
3.
40). Start over with step 1.
Press the Off button once to toggle the selected option on or off.
4.
Repeat steps 2 and 3 for each option.
5.
To save the configuration settings and exit Configure mode, press and hold the Test/Alarm Reset
6.
button for 3 seconds.
NOTE: Configure mode times out after 2 minutes of inactivity. If the Test/Alarm Reset button
has not been pressed, any new selections are not saved.
For the location of buttons, see "UPS front panel controls (on page 7)."
For the location of LEDs, see "UPS front panel LED indicators (on page 7)."

Initiating a self-test

To initiate a self-test, press and hold the Test/Alarm Reset button
for three seconds.
If the UPS detects a problem, the appropriate LED
illuminates and an audible alarm may sound.
For information on what to do if the self-test detects a problem, see "Troubleshooting (on page 54)."

Silencing an audible alarm

To silence an alarm, press the Test/Alarm Reset button
IMPORTANT:
• Although the audible alarm silences, the condition that caused the alarm to sound may still
exist.
• If a utility power failure caused the alarm, the alarm silences after power is restored.
For information about audible alarm conditions, see "LED and audible alarm troubleshooting
troubleshooting" on page 54)."
Associated LED Explanation (when LED is
127/240 Nom
Overtemperature
Wiring fault
Overload
illuminated)
Nominal output voltage is 127 V for a low
voltage model and 240 V for a high voltage
model
Audible alarm will sound when ground is
missing or line and neutral connections are
reversed
("UPS front panel
("UPS front panel LED
indicators" on page 7)
("UPS front panel
controls" on page 7).
controls" on page 7)
("LED
UPS operations 43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents