High-voltage UPS battery runtimes
Load, percent
20
50
80
100
Low-voltage UPS battery runtimes
Load, percent
20
50
80
100
Environmental specifications
Feature
Operating temperature
Nonoperating
temperature
Relative humidity
Operating altitude
Nonoperating altitude
Audible noise
REPO port specifications
The REPO port meets the requirements of NFPA 70 and NEC Articles 645-10 and 645-11 for a
Disconnecting Means.
Estimated battery
Runtime with one ERM
runtime
40 minutes
125 minutes
12 minutes
50 minutes
6 minutes
30 minutes
4 minutes
24 minutes
Estimated battery
Runtime with one ERM
runtime
45 minutes
142 minutes
15.5 minutes
55 minutes
7 minutes
34 minutes
5 minutes
26 minutes
Specification
10°C to 40°C (50°F to 104°F); UL-tested at 25°C
(77°F)
-15°C to 40°C (-5°F to 104°F)
20% to 80%; noncondensing
Up to 3,000 m (9,842 ft) above sea level
15,000 m (49,212 ft) above sea level
Less than 45 dBA, normal operation
Less than 50 dBA, on battery power
Runtime with two ERMs
225 minutes
89 minutes
54 minutes
43 minutes
Runtime with two ERMs
256 minutes
99 minutes
60 minutes
47 minutes
Specifications 62