8-4-2-1. Network No.
Network configuration is required only when a BACnet
(Only [Local] will appear in the Network No. column when no BACnet
The maximum number of network that can be configured is 5 (including Local).
Click [Add] to display the [Network No.] popup window. Enter the network information in the fields.
No.
Item
1
Network No.
2
Type
®
BACnet
Router
3
IP Address
4
Port No.
WT07921X01
Enter the network number.
(Setting range: 1 to 65534)
Set to "65535" when using Global Broad Cast.
IP (fixed)
Enter the IP address of the BACnet
network that was configured in No. 1 above.
(The IP address of the BACnet
AE-200 is connected.)
The number of the port that the BACnet
communication appears here.
Leave [47808] as it is unless otherwise specified.
39
®
router is used.
®
router is used.)
Description
®
router to be connected to the
®
router on the network to which the
®
router uses for BACnet
Default
(Blank)
IP
(Blank)
®
47808