Mitsubishi Electric AE-200A Instruction Book page 32

Control system/centralized controller
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

8-2-1-2. LAN2 (for BACnet
Sets fields for the AE-200 LAN2 (for BACnet
set using IPv4.
No.
Item
1
IP Address
2
Subnet Mask
3
Default Gateway
4
BACnet Port No.
*1 Normally, set as in the following table based on the leading octet value of the IP address. (Figures within parentheses indicate the
private IP address.)
No.
IP address leading octet value
1
1 to 126
2
128 to 191
3
192 to 223
Setting the wrong IP address may impact other devices connected to BACnet
IP address used by the AE-200 is set correctly.
8-2-1-3. Unit of Temperature
Select a desired temperature unit to be used. (Default setting: [degrees-Celsius])
Check the radio button next to [degrees-Celsius] to display the temperatures in ºC.
Check the radio button next to [degrees-Fahrenheit] to display the temperatures in ºF.
8-2-1-4. Use AE-200/AE-50/EW-50 Time Synchronization
If reflecting the time data sent from the central monitoring device to the AE-200 or M-NET system (indoor
units, remote controllers, or system controllers), select this check box.
(Default value: not selected (do not synchronize time to AE-200 or M-NET system))
WT07921X01
®
)
®
) IP address (some items are display-only). LAN2 can only be
Set the IP address of AE-200 (LAN2).
Set the IP address network address portion.
When using an IP router for BACnet
IP address of the IP router.
If not using an IP router, do not set this.
Display the port number used by the AE-200 for BACnet
communications.
Subnet mask to set
(10)
255.
0.
(172)
255.255.
(192)
255.255.255.
Description
®
communications, set the
0.
0
0.
0
0
32
Default value
192.168.2.1
*1
255.255.255.0
*1
(Blank)
®
47808
®
, therefore ensure the