Mitsubishi Electric AE-200A Instruction Book page 49

Control system/centralized controller
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

(1) Objects used for temperature setting commands from the central monitoring device
Temperature setting objects that can be used differ depending on indoor unit group configuration. When
setting temperature from the central monitoring device, use temperature setting objects that match the indoor
unit group configuration.
Groups for which "Old Model Compatibility Mode" is off, and groups within which all indoor units support
"Dual-set-point mode in the Auto mode" are groups that support "Dual-set-point mode in the Auto mode".
Groups for which "Old Model Compatibility Mode" is on, or groups within which there are indoor units that do
not support "Dual-set-point mode in the Auto mode" are groups that do NOT support "Dual-set-point mode in
the Auto mode".
For groups supporting dual-set-point mode, issue commands using dual-set-point mode objects (AV_xxxx24
to AV_xxxx28); and for groups not supporting dual-set-point mode, issue commands using indoor temperature
set value objects (AV_xxxx10).
If the central monitoring device issues a command for groups that do not support dual-set-point mode using a
dual-set-point mode object, then the AE-200 will return an error to the central monitoring device.
Central monitoring
device
Sends request using
dual-set-point mode
object to indoor unit
group 1
Sends request using
dual-set-point mode
object to indoor unit
group 2
Sends request using
indoor temperature
set value object to
indoor unit group 2
Select the temperature setting objects according to the indoor unit group configuration in a given air
conditioning system.
AV_xxxx10 Set Temp
AV_xxxx24 Set TempCool
AV_xxxx25 Set TempHeat
AV_xxxx26 Set TempAuto
AV_xxxx27 Set High Limit
SetbackTemp
AV_xxxx28 Set Low Limit
SetbackTemp
*1 The mode can be switched from a remote controller. The mode cannot be switched on the AE-200's LCD. (The mode can not be
switched on some models of indoor unit.)
*2 These objects can be selected when the indoor unit group supports the Setback function.
WT07921X01
®
BACnet
AE-200 BACnet
function
AV_xxxx24–28
AV_xxxx10
AV_xxxx24–28
Error returns.
AV_xxxx10
Group 2 does not support dual-set-point mode, therefore if the central
monitoring device issues a command using a dual-set-point mode object,
then the AE-200 will return an error to the central monitoring device.
Groups that do not
support the dual-set-point
mode in the Auto mode
M-NET
®
Sends the set
temperature to the
group.
Not send the set
temperature to the
group.
Sends the set temperature to
the group.
Indoor unit group configuration in the air conditioning system
Groups that support the dual-set-point mode
Dual-set-point mode
V
49
Indoor unit group 1
(Group that supports dual-set-
point mode in the Auto mode).
Indoor unit group 2
×
(Group that does not support dual-
set-point mode in the Auto mode)
in the Auto mode
*1
Single-set-point mode
V
V
*2
V: Available
—: Not available
*1
V
V
V
*2