Calibrating The Measuring Voltage Input Of Neutral Conductor Vn; Calibrating Sicam Mmu (Potential Divider Voltage Measurement) - Siemens SICAM MMU 7KG9663 Device Manual

Table of Contents

Advertisement

10.4

Calibrating the Measuring Voltage Input of Neutral Conductor VN

10.4.1

Calibrating SICAM MMU (Potential Divider Voltage Measurement)

Measurement Setup
Fig. 10-7
Measuring Ranges
You can perform the calibration for the following alternating-voltage measuring ranges:
AC 63.5 V
AC 110 V
AC 230 V
AC 400 V
Calibration
To calibrate the alternating-voltage measuring ranges, proceed as follows:
Set up the measurement as shown in figure 10-7 or figure 10-10, acc. to device version.
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Measurement Setup for Calibrating VN
10.4 Calibrating the Measuring Voltage Input of Neutral Conductor VN
Reference
Voltage
Output
N
10 Calibration
207