Sdi Address 88; D9133Dc Direct Connect Programming Module; Connecting The D9133Dc; Used As An External Modem - Radionics D9412G Operation And Installation Manual

Control/communicators
Table of Contents

Advertisement

11.6

SDI Address 88

SDI Address 88 is available with the D9412G/D7412G panels and is used for several different applications. When
using SDI Address 88, only one of the listed devices may be connected at a time.

11.6.1 D9133DC Direct Connect Programming Module

The D9133DC Direct Connect Programming Module can be used to locally program the D9412G/D7412G panels.
In addition to this, the D9133DC allows Diagnostics and History retrieval to be performed. The D9133DC is not UL
Listed.

11.6.1.1 Connecting the D9133DC

1.
Configure the D9133DC for SDI Address 88. To program the panel when the reset pin is in the unlocked
position, program Enable SDI RAM to Yes in the RADXAUX1 handler.
2.
Connect the D9133DC to Com Port 1 or Com Port 2 on the PC. The D9133DC has a DB-9 female serial
connector. A null modem cable must be purchased separately to connect the D9133DC to a PC.
3.
Using 22 AWG or 18 AWG wire, connect the D9133DC SDI terminals (SDI PWR, SDI A, SDI B, and SDI COM) to
the panel's SDI terminals (Terminals 29 to 32).
To send or receive the panel's program, the Reset Pin can be in the Locked or Unlocked position.
Note :
Locking the Reset Pin when programming the panel improves upload/download time.

11.6.1.2 Used as an External Modem

The D9133DC can also be used as an external modem when using RAM IV with the panel. Please see the
D9412G/D7412G Program Entry Guide for programming details.

11.6.2 D9133TTL-E Network Interface Module

The Radionics D9133TTL-E Network Interface Module is a four-wire powered SDI device providing connection for
bi-directional communication over Ethernet networks to D9412G/D7412G panels. For programming information on
enhanced communications, please refer to the D9412G/D7412G Program Entry Guide .
The D9133TTL-E can be installed up to 1,000 ft. (305 m) away from the panel using 18 AWG wire.

11.6.3 Address Settings

D9133TTL-E Network Interface Module
A jumper must be placed over Pin 8 for the D9133TTL-E (SDI
Address 88) to be used for RAM IV and/or enhanced
communications in a LAN/WAN environment.

11.6.4 Supervision

Supervision of the D9133DC, D9133TTL-E, and D9133TTL-TR at SDI Address 88 is available through
programming that ensures operation between the module and the control panel.
If supervised and the module does not respond to panel supervision polls, SERVC SDI 88 displays at the
command center. The report to the receiver includes the address of the troubled module to indicate which module
needs service.
© 2002 Radionics
D9412G/D7412G Operation & Installation Guide
Page 59