D9412G/D7412G
Power Supply
4.2.6
Battery Discharge/Recharge Schedule
Discharge Cycle
AC OFF
13.9 VDC
13.8 VDC
12.1 VDC
10.2 VDC
Recharge Cycle
AC ON
13.7 VDC
13.9 VDC
4.3
Charging Status and Low Battery LEDs
Type
Charging
Status
LED
and Red
Low
Battery
LED
Red and
43488D
AC fail report when AC fails if panel is
programmed to report AC failure at
occurrence.
Charging float level
Charging Status LED on
Low Battery & AC fail reports if
programmed; Low Battery LED on
Battery load shed (processing
functions continue if AC is
present)
Load shed relay resets, battery
charging begins, battery trouble
and AC restoral reports sent.
Battery restoral reports sent, Low
Battery LED off
Charging Status LED off, battery
float charged
LED
LED
Action
Color
State
Yellow
Shows the charging status of the battery. Figure 6 shows its location.
Yellow
Off
Battery is fully charged.
If the battery is missing, shorted, or reversed: The Charging Status
LED is off, but the red Low Battery LED is flashing.
Yellow
On
Battery float charge is below 13.8 VDC. If AC is present the battery is
charging.
When the combined current draw from all outputs exceeds 1.4 amps.
This is normal under alarm conditions for non-fire systems with sirens or
bells draw more than 1.4 amps. If the LED comes on regularly for
extended periods or doesn't go out, check the current draw for devices
connected to the power outputs. See section 5.0 Power Outputs for
instructions.
Yellow
System is checking the battery.
Flash
once/min
Yellow
Flash
When the current draw for devices connected to the power outputs
once/min
exceeds 1.4 amps and/or the battery is missing.
Red
Shows the condition of the battery. Figure 6 shows its location.
Red
Off
When the battery is fully charged.
Red
On
Battery voltage as fallen below 12.1 VDC. LED goes out when voltage
reaches 13.7 VDC.
Red
Flash
Green LED is Operation Monitor LED.
(same
Battery is missing or shorted.
rate as
Green
LED)
Flash
When current draw for devices connected to the power outputs exceeds
Yellow
once/min
1.4 amps and/or the battery is missing.
Table 7: Charging Status and Low Battery LEDs
D9412G/D7412G Operation & Installation Guide
Figure 6: Charging and Battery LEDs
Page 28
LEDs Off When Normal
Charging Status
YEL
Low Battery
RED
© 2002 Radionics