Advertisement

D2112/D2112E Control/Communicator
Installation Manual
D2112/D2112E Installation Manual
Page 1
74-07111-000-D 1/96
© 1995 Radionics

Advertisement

Table of Contents
loading

Summary of Contents for Radionics D2112

  • Page 1 D2112/D2112E Control/Communicator Installation Manual D2112/D2112E Installation Manual Page 1 74-07111-000-D 1/96 © 1995 Radionics...
  • Page 2: Notice

    An example of the facilities, equipment, operations, or procedures that line is shown in the margin to the left of this could affect the operation of the D2112. If this paragraph. happens, the telephone company will provide...
  • Page 3: Table Of Contents

    D2112/D2112E Control/Communicator .... 4 Terminals 15 to 22 (14 to 22 on D2112E) ..10 Ordered Separately .......... 4 Points 7 and 8 on the D2112 Only Enclosure Options ..........4 Terminals 23 to 25 .......... 10 Listings and Approvals ........4 Program the Panel ..........
  • Page 4: Introduction

    Introduction Enclosure Options The D2112 and D2112E are shipped in the D2103 D2112/D2112E Control/Communicator enclosure. If you want to mount the D2112 or The Radionics D2112 and D2112E Control/ D2112E in one of the optional enclosures listed Communicators are shipped pre-assembled from the below, order the D2112M or D2112EM, and the factory.
  • Page 5: Mount The Enclosure

    • High voltage electrical equipment (Electro-Magnetic Interference) problems. • PBX telephone system On the D2112, wire resistance on the Point 1 sensor • Public service (police, fire departments, etc.) loop must be less than 50Ω. Measure the wire using radio communications resistance before installing smoke detectors.
  • Page 6: Connect Earth Ground Terminal 3

    Lock the pin down now. See burglary systems: In order to meet standby battery Figure 2. requirements, use the Radionics D126, 12 V 7.0Ah With the Standby Switch locked down, the panel battery for fire and combined fire/burglary systems.
  • Page 7: Install Detection Devices, Keypads, And Bells

    Radionics D126, 12 V 7.0Ah battery for fire and combined fire/burglary systems. When using the D2112's Point 1 as a fire point, the number of devices you can connect to it's sensor Power restricted for fire and combined fire/ loop is limited.
  • Page 8: Keypads

    Outputs on page 14 to determine the total power the keypad. For more information about this and output requirements for your system. Instructions for other keypad diagnostic features, see the D2112 using stand alone power supplies are included. Keypad Diagnostics manual (74-07113-000).
  • Page 9: Testing And Replacing D2112E Fuses

    The D2112E's Aux Power and Bell outputs are protected by 2 Amp fast blow fuses. The fuses are 5 mm x 20 mm, 2 Amp Fast Blow (Radionics Part # 57-03570-008). To test the fuses, use a Volt/Ohm meter to follow these steps: 1.
  • Page 10: Connect The Points

    Connect up to five Radionics D262 two-wire smoke function. See RELAYS in the D2112/D2112E detectors to point 1 on the D2112. Refer to the Program Entry Guide for programming instructions. Technogram, Smoke Detectors Compatible with the...
  • Page 11 8.9 - 13.9VDC Normal 2.5 - 8.5VDC Short 0.0 - 2.0VDC 1.0 K Ω Resistor Required at End of Line USED USED Point Point Point Point Point Point Figure 6: Points D2112/D2112E Installation Manual Page 11 74-07111-000-D 1/96 © 1995 Radionics...
  • Page 12: Program The Panel

    Connect the battery and then plug in the programmed Point 1 for Fire with Verification transformer. (Digit 1 = 2). See POINT CODES in the D2112/ Leave the Standby Switch locked down for now. D2112E Program Entry Guide for more information.
  • Page 13: Test The System

    Larger Battery Increases Backup Time: To 13.0 VDC Battery restoral reports sent, OK increase battery backup time, connect a larger light on steady capacity battery, up to 7 Ah (Radionics D126). 13.9 VDC Battery float charged D2112/D2112E Installation Manual Page 13 74-07111-000-D 1/96 ©...
  • Page 14: Power Outputs

    You can program the panel to use DTMF or pulse both the auxiliary and alarm power outputs. dialing. See Phone Parameters in the D2112/ D2112 bell circuit protection: A short on alarm D2112E Program Entry Guide . power output while the bell is ringing disables the...
  • Page 15: Points

    Point 1 is a powered sensor loop. Review the You can connect a momentary contact arming Radionics Technogram: Smoke Detectors station (keyswitch) to turn the D2112 on and off. The Compatible with the D2112 (73-07115-000) for a list keyswitch is connected to a point sensor loop (points of compatible detectors.
  • Page 16 Keyswitch Operation Easikey Shorting and restoring the point sensor loop toggles You can use a Radionics Easikey access system to the system On and Off. All faulted points are turn the system Off. Program the Keyswitch Keyswitch prompt bypassed. See POINT CODES Group in the D2112/ to Easikey.
  • Page 17: Installation Guide For Ul Applications

    System Chart. See the for Standby Battery Calculations. installation and operation instructions for each D2112 only: Two-wire detectors must be electrically component for detailed instructions. compatible, and must be UL listed for use with the D2112.
  • Page 18: Current Rating Chart For Standby Battery Calculations

    1 If Total A exceeds 860 mA, a stand-alone power supply is required to provide additional current. 2 If Total C exceeds 860 mA for fire systems, a stand-alone power supply is required to provide additional current. D2112/D2112E Installation Manual Page 18 74-07111-000-D 196...
  • Page 19: System Chart

    System Chart D2112 and D2112E not listed for these applications NFPA Standard 71, 72 71, 72 Minimum Hours 24 + 24 + of Standby 4 mins 4 mins Battery alarm alarm No = Not acceptable for this application Included with panel.
  • Page 20: System Wiring Diagram, Issue A

    Battery 12V 7Ah 12V 4Ah 16 VAC D8004 Aux Power Fuse Alarm Output Fuse 25 VA D1625 Transformer 2 Amp Fast Blow 2 Amp Fast Blow Enclosure 60 HZ Transformer D2112/D2112E Installation Manual Page 20 74-07111-000-D 196 © 1995 Radionics...
  • Page 21: Specifications

    9 (140mA for Fire Compatible Accessories (D2112 and D2112E) and combined Fire/Burglary systems) . See the Radionics Product Catalog for complete list. Alarm Power Output • D126 12V, 7 Ah Rechargeable Battery • 1.5 A maximum at 10.2 VDC to 13.9 VDC output.
  • Page 22: D2112/D2112E Terminal Quick Reference

    Ring of incoming phone line Ring of phone line to premises phone ™The Radionics logo is a registered trademark of Radionics, Inc., Salinas, CA, U.S.A. ©1994 Radionics, Inc., Salinas, CA, U.S.A. All rights reserved Radionics, Inc., 1800 Abbott Street Radionics, 1 Park Gate Close, Bredbury...
  • Page 23 O&I Menu Documents by Type Menu Documents by Product Menu Main Menu...