9.2

D811 Arm Status Relay Module

The D811 Arm Status Relay Module allows the addition of a single off-board relay output to the system. Alarm
output, auxiliary relay, sensor reset, arming status, point status, alarm memory, or remote functions can be
assigned to the D811 relay output. It is not restricted to the arming status mode only.
Relay numbers for D811 not programmable: If the D811 is connected to ZONEX 1, Terminal 28, relay number 53
must be used for the relay output. If the D811 is connected to ZONEX 2, Terminal 26 on the D9412G, relay number
117 must be used for the relay output.
D811 Modules connect as shown in Figure 18a and Figure 18b . Review section 5.0 Power Outputs to be sure to
provide enough power for the powered devices that will be connected to the system. See Relay Parameters in the
D9412G/D7412G Program Entry Guide for programming details.
D811 restricted for fire systems: The D811 relay output is not supervised and cannot be used in fire or combined
fire/burglary installations for primary indication devices.
9.2.1

Relay Output

Each D811 relay output provides a Form C dry contact rated for 1.0 A at 12 VDC. Normally-open, common, and
normally-closed terminals are available. When an individual output is activated, there is continuity between the
normally-open and common terminals. When the output is not activated, there is continuity between the normally-
closed and common terminals.
Relay outputs may activate while programming the panel. You may wish to disconnect equipment
connected to relay outputs while performing these functions.
9.2.2

Installation

Install the D811 in the enclosure with the panel (see Figure 2 ) or in an adjacent enclosure NOT
MORE THAN 5 FT. (1.5 M) from the panel. Use 16 to 22 AWG wire.
Follow the procedure below to install D811 Modules in the enclosure with the panel.
1.
Align the D811 Module with any of the four mounting locations in the enclosure. See Figure 2 .
2.
Use the screws provided with the module to secure it in the enclosure.
Use the D137 Mounting Bracket or D9002 Mounting Skirt to install D811 Modules in enclosures with no module
mounting locations available.
9.2.3

Wiring Connections

Power down the panel to connect D811 Modules as shown in Figure 18a and Figure 18b . Note that the D811 for
relay number 53 connects to ZONEX 1. The D811 for relay number 117 connects to ZONEX 2 on the D9412G.
2 1
© 2002 Radionics
R es et P in
Disa ble A ll E xc ep t B attery
C h arg in g A n d P ro g ra m m in g
PE RIPH ERA L DE VICE CO NN ECTION S
R ED
PO WER +
3 2
3 1
YE LLO W
D ATA BU S A
G REE N
D ATA BU S B
3 0
2 9
B LACK
CO M M ON
N .F.P.A.
ZO NEX OU T 1
2 8
Style 3.5
Signaling
Line
C ircuits
ZO NE X IN 1
2 7
2 6
ZO NEX OU T 2
2 5
ZO NE X IN 2
2 4
ZON EX P OW ER +
2 3
ZO NEX CO M M ON
P o int 8
PRO G
G N D FA U LT
CO NN
De tec t
D
E
I
N
S
A
A
B
B
L
2 2
L
G R N
E
E
O n -B oa rd P oints

Figure 18a: D811 Module Wiring to the D9412G

D9412G/D7412G Operation & Installation Guide
DATA
D811 FOR RELAY NUMBER 53
AUX
GND
DATA
AUX
D811 FOR RELAY NUMBER 117
GND
Page 51
D9412G/D7412G
Off-board Relays
5
5
43488D