6.0

Telephone Connections

6.1

Registration

The Radionics D9412G/D7412G Control/Communicator panels are registered with the Federal Communication
Commission under part 68, for connection to the public telephone system using an RJ31X or RJ38X jack installed
by the local phone company.
Note:
An RJ31X jack can be modified by placing a jumper wire between Terminals 2 and 7 to become an RJ38X jack.
6.2

Notification

Do not connect registered equipment to party lines or coin-operated telephones. The local telephone company
must be notified and supplied with the following information before connecting the panel to the telephone network:
The particular line to which the panel will be connected
Make (Radionics), model (D9412G or D7412G), and serial number of the panel
FCC registration number and ringer equivalence for the panel:
FCC Registration Number: AJ9MUL-46532-AL-E
Ringer Equivalence: 0.1B
6.3

Location

To prevent jamming of signals, wire the RJ31X or RJ38X
jack before the in-house phone system to support line
seizure. See Figure 8 . Install the jack on the street side of
the phone switch, wired ahead of any PBX equipment. Line
seizure provides for a temporary interruption of normal
phone usage while the communicator transmits data. After
installation, confirm that the panel seizes the line, acquires
dial tone, reports correctly to the receiver, and releases the
phone line to the in-house phone system.
6.4

Phone Cord Connection

Connect one end of a D161 (7 ft. [2.1 m]) or D162 (2 ft. [61
cm]) Telephone Cord to the TELCO Cord connector located
on the bottom left corner of the panel. See Figure 9 .
Connect the other end to the RJ31X or RJ38X jack.
Note:
To supervise the phone cord, use an RJ38X jack.
Telephone Cord
Connector

Figure 9: Phone Connector and LED and Operation Monitor LED Locations

6.5

Phone LED (Red)

The red Phone LED lights when the panel seizes the phone line and remains lit until the panel returns the phone
line. See Figure 9 for the location of the red LED.
© 2002 Radionics
GROUND START
PHONE
RED
Requires
LED
Relay # D136 in
11
12
13
ON WHEN
Ground
COMMUNICATING
Start Socket
OFF WHEN IDLE
Phone LED
(Red)
D9412G/D7412G Operation & Installation Guide
(TIP)
Outside
TELCO
14
15
16
17
18
19
20
Operation Monitor
LED (Green)
Page 33
D9412G/D7412G
Telephone Connections
RJ31X
RING (red)
TIP (green)
R1
T
R
1
2
4
5
1
4
5
(RING)
1
4
5
Premises
Telephone

Figure 8: RJ31X Wiring

D
E
I
N
S
A
A
B
B
L
21
22
L
GRN
E
E
RJ31X
Jack
T1
7
8
8
TELCO
Connector
Block
8