Specifications; Table 4: Specifications - Radionics D9412G Operation And Installation Manual

Control/communicators
Table of Contents

Advertisement

D9412G/D7412G
Overview
2.2

Specifications

(The black and white circles with numbers indicate the specific panel terminal.)
Voltage Input
(Power Supply)
Current Requirements
Power Outputs
Minimum Operating
Voltage
SDI Bus
Telephone Connections
43488D
Primary:
Secondary:
Panel : 500 mA alarm, 200 mA idle
See Current Rating Chart for Standby Battery Calculations in the D9412G/D7412G
Approved Applications Compliance Guide for the current draw requirements of other
system components.
All external connections are inherently power-limited except battery terminals.
Continuous Power
Outputs
Alarm Power
Output
Switched Aux
Power
Fire and
To comply with UL 985 and 864 listing standards for fire alarm
Fire/Burglary
systems (effective March 1, 1989), the total combined
Systems
continuous and alarm current draw for the system during alarm
conditions must be limited to 1.4 A (1400 mA) provided by the
primary power supply (rectified AC). If current draw for the
system exceeds 1.4 A, remove connected devices until the
current draw falls below 1.4 A, then connect the removed
devices to a D8132 Battery Charger Module or to an external
power supply (see Figure 19 ).
10.2 VDC
SDI Bus A (+):
9 VDC (15,000 ft. [4,572 m] max.)
SDI Bus B (-):
9 VDC (15,000 ft. [4,572 m] max.)
Connection
RJ31X or RJ38X jack can be interfaced with the panels.
Two TelCo Lines
Radionics D928 Dual Phone Line Module required for two
phone line service. Supervision supplied by the panel.

Table 4: Specifications

D9412G/D7412G Operation & Installation Guide
Page 14
16.5 VAC 40 VA class 2 plug-in
transformer (D1640)
Sealed lead-acid rechargeable
(12 VDC, 7 Ah or 12 VDC, 17.2
or 18 Ah) battery. The panel
supports a maximum of two 12
VDC, 7 Ah batteries using the
D122 Dual Battery Harness or
two D1218 (12 VDC, 17.2 or 18
Ah) batteries using a D122.
1.4 A maximum at 10.2 VDC to
13.9 VDC (continuous supply)
total for all devices and outputs
supplied at Terminals 3, 24, and
32 and at the Accessory and
Programming Connectors.
2.0 A maximum at 10.2 VDC to
13.9 VDC output. Output may be
steady or one of three pulsed
patterns depending on
programming. See Relays in the
D9412G/D7412G Program Entry
Guide .
1.4 A maximum at 10.2 VDC to
13.9 VDC output. Continuous
output is interrupted by Sensor
Reset or alarm verification
depending on programming. See
Relays in the D9412G/D7412G
Program Entry Guide .
© 2002 Radionics