D9412G/D7412G
Installation
3.6.6

Power Up

Reconnect the battery and then plug in the transformer. Remember the buzzer sounds for two seconds when the
panel is first powered up.
Leave the reset pin locked down for now.
Yellow Charging Status LED doesn't go out: If the yellow charging status LED doesn't go out within five minutes
of powering up the panel, the battery may be deeply discharged, or too many powered devices have been
connected to the panel. Combined continuous current draw for Terminals 3, 8, 24, and 32, and the Accessory
Connector cannot exceed 1.4 amp. See section 5.0 Power Outputs for help.
3.7

Programming the Panel

If a program hasn't been created for the panel, review the D9412G/D7412G Program Entry Guide . Check to be
certain all the required accessory modules to be installed for desired features are available. The reset pin must be
in the locked position to copy or send information to and from the panel.
Use the D5200 Programmer or the Remote Account Manager (RAM IV) to load a custom program into the panel.
Move the reset pin to the normal position. See Figure 3 . The panel transmits reboot and battery reports to the
receiver if programmed for reporting.
3.8

Install the Point Chart Label

Radionics recommends the Point Chart Label provided in the literature pack be filled out and installed on the
inside of the enclosure door for all systems.
Point chart label required for fire systems with verification points: The point chart label must be installed for fire
or combined fire/burglary systems using verification points.
Use the D9412G/D7412G Program Record Sheet to gather the information needed to fill out the point chart. Install
the label on the enclosure door as shown in Figure 2 . To avoid smearing the entries on the chart, use the label's
peel off backing to press the label in place.
3.9

Testing the System

After finishing the installation and programming of the panel, make a complete functional test of the system. Test
the panel and all devices for proper operation. Test after first programming the panel and after any subsequent
programming session.
Service Walk Test shows extra points: Use the service walk test at a panel wide command center to perform a
complete test of the panel. The service walk test function is similar to the ordinary walk test function, with the
additional ability to display points that are not properly programmed.
During a Service Walk Test, a tested POPIT with its switches set for a point with a blank point index and/or no area
assignment, appears as an extra point.
If a device is tested and the panel doesn't respond, there may be a problem with the device, the wiring, the POPIT
ID setting, or the programming for the point. If the switches on a POPIT are set incorrectly, it may create both a
missing and extra point. When a missing point is found, performing a service walk test for extra points may help
diagnose the problem.
See the D9412G/D7412G Installation and Troubleshooting Quick Reference Guide for complete service walk test
instructions.
Clear after test: To clear the event memory and report buffer, momentarily close the reset pin. Events stored in
the panel's event log are not cleared.