11.0 SDI Devices

11.1

Description

The D9412G/D7412G panels can support a number of accessory devices off the SDI bus using Terminals 29
through 32. Some devices include the D1255 Command Center (discussed in the previous section), the D9131A
Parallel Printer Interface Module, the D9210B Wiegand
Module, and the D9133TTL-E Network Interface Module.
11.2

Installation

Consult the Operation and Installation Guide of the specific SDI device for complete installation instructions. SDI
devices connect to the panel in parallel as shown in Table 14 .
These devices may share power with the panel or be powered by a stand-alone power source.
A stand-alone power supply powering any SDI device must also be connected to a common terminal
on the panel. Do not connect the stand-alone power supply's earth ground to Terminal 10 on the
panel.
11.3

D9131A Parallel Printer Interface Module

The Radionics D9131A Parallel Printer Interface Module is a 4-wire powered device used to connect a standard
parallel printer to a panel. The D9412G can supervise three printers, and the D7412G can supervise one printer.
Each printer requires a separate D9131A Parallel Printer Interface Module. The D9131A connects to the printer
using a standard parallel printer cable.

11.3.1 Switch Settings

Switches on the D9131A assign a unique address (17
to 19) to each printer. The address determines if the
printer is supervised, the printer's scope, and the area
to which the printer is assigned. See Printer Parameters
in the D9412G/D7412G Program Entry Guide for a
complete description of addresses.
Table 15 shows the correct switch setting for each
address.

11.3.2 Supervision

Supervision includes proper operation of the SDI bus, proper connection of the printer cable between the printer
and the D9131A, printer paper supply, printer selected (on-line), and printer power.
The panel sends an SDI failure report to the receiver if it fails to communicate with the printer interface, and SERVC
PRINTER displays at the command center. The report to the receiver includes the address of the troubled D9131A
to indicate which printer needs service.
If an SDI device is supervised and SDI A becomes disconnected, the device may still operate normally, depending
upon environmental conditions.
© 2002 Radionics
D9412G/D7412G
Terminal
Function
32
POWER +
31
DATA BUS A
30
DATA BUS B
29
COMMON

Table 14: SDI Device Connections

D9412G/D7412G Operation & Installation Guide
TM
Control Interface Module, the D9133 Serial Interface
SDI Devices
Wire Color
Function
Red
+12 VDC
Yellow
Green
Data-Out
Black
Common
Printer
1
17
ON
=
18
OFF
=
19
ON
=
= D9412G only
* ON = Header and Form Feed
OFF = No Header and No Form Feed

Table 15: Printer Address Switch Settings

Page 57
D9412G/D7412G
SDI Devices
Data-In
Switch
2
3
4
ON
ON
*
ON
ON
*
OFF
ON
*
5
6
ON
ON
ON
ON
ON
ON
43488D