5.4.5

Terminal 8

Terminal 8 provides continuous positive (+) 10.2 VDC to 13.9 VDC power. Relay C interrupts the power at Terminal
8 when activated. Use Terminal 8 to power smoke detectors or other devices that are reset by interrupting power.
One self-resetting circuit breaker protects Terminals 6, 7, and 8 against shorts.
Verification/Reset Relay
The default program sets Relay C (Terminal 8) as a verification/reset relay. See Relay Parameters and Point
Assignments in the D9412G/D7412G Program Entry Guide for instructions on programming verification/reset
relays and points.
Performing a Sensor Reset at a command center produces a five second relay activation of verification/reset
relays. The panel ignores verification/reset points during the five seconds of relay activation.
© 2002 Radionics
D9412G/D7412G Operation & Installation Guide
Page 31