Wiring Information For Installations Using The Ademco Ab-12 Bell/Housing; Figure 13: Wiring For Installations Using The Ademco Ab-12 Bell/Housing - Radionics D9412G Operation And Installation Manual

Control/communicators
Table of Contents

Advertisement

D9412G/D7412G
On-board Points
7.5

Wiring Information for Installations using the Ademco AB-12 Bell/Housing

1 2 3 4 5 6
Bell
Inner Bell
Box Lining
Outer
Bell Box

Figure 13: Wiring for Installations using the Ademco AB-12 Bell/Housing

1.
Disconnect the wire jumper from Terminal 4 to the inner housing of the Bell Box (prevents a ground fault
condition).
2.
Connect wiring between the control and Bell Box as shown above. To use the AB-12 Bell/Housing, place the
S3 switch in the disabled (open) position. The EOL used in the AB-12 Bell/Housing must be a 220 kΩ, 0.5 W
resistor.
3.
Program Point 8 as 24-hour, ALARM on open and short. (PT TYPE 0, PT RESPONSE 0).
43488D
43489F
LEDs Off When Normal
YEL
Charging Status
Low Battery - 12.1 VDC
RED
10.2 VDC - Battery Load Shed
CLASS 2 TRANSFORMER
The Power Supply Provides a Maximum of 1.4 Amps For The Control
1
16.5 VAC 40 VA 60 Hz
Panel and All Accessory Devices. For System Loading, See Operation-
Part No. D1640
Installation Manual #43488 ___.
Internally Fused - Do Not short
All External Connections Except Terminal 5 (Battery Positive) Are
Requires Unswitched Outlet
2
Inherently Power Limited.
Do Not Share With Other Equipment
Requirements For Battery Standby Time May Reduce Allowable Output.
+ AUX POWER
CAUTION:
3
WARNING!
BATTERY NEGATIVE ONLY
4
Multi-Battery Installation Requires
Maximum Charging
Model No. D122 Dual Battery Harness.
Current 1.4 Amps.
Improper Installation Can Be a Fire
5
BATTERY POSITIVE ONLY
Hazard.
PROGRAMMABLE
This equipment should be installed in accordance with the NFPA 70 (National Electrical Code)
RELAY A
6
ALARM OUTPUTS
and NFPA 72 (National Fire Alarm Code) for Local, Central Station, Remote Station and Household Fire
Terminals
Warning Systems and under the limits of the Local Authority Having Jurisdiction (National Fire
7
&
8
Protection Association, Batterymarch Park, Quincy, MA 02269) Printed information describing proper
RELAY B
7
installation, operation, testing, maintenance, evacuation planning and repair service is to be provided
Requires Optional
with this equipment.
D136 Relay
In ALT ALARM
RELAY C
8
D9412G Control / Communicator is UL Listed For Central Station, Local, Remote Station and Household
& SW AUX
Fire Alarm, and Central Station, Local, Police Station Connect and Household Burglar Alarm.
System is Intended To Be Checked By A Qualified Technician At Least Every 3 Years.
9
COMMON
10
EARTH GROUND
GROUND FAULT DETECT
Point 1 Point 2
Enabled
Disabled
PHONE MONITOR SELECT
LOOP START
GND START
GROUND START
PHONE
Requires
RED
LED
11
Relay # D136 in
ON WHEN
Ground
COMMUNICATING
Start Socket
OFF WHEN IDLE
B
e
l
EOL
l
220 kΩ
½ W
T
a
m
p
e
r
s
D9412G/D7412G Operation & Installation Guide
Page 38
Digital Alarm Communicator Transmitter
Reference Manual #43494 ___ For System Wiring Diagram, Issue A
Reference Document #33284 ___ For Compatible Smoke Detectors
POWER SUPPLY REQUIREMENTS
See Manual For Power Requirements Relating to Terminals 6
Battery: Replace Every 3 to
5 years with Model D126, 12 V
7 Amp Hr Lead Acid Battery
The types of initiating circuits that the panel has been approved for are A, M, W, SS.
VOLTAGE RANGES
Open
3.7 - 5.0 VDC
Normal
2.0 - 3.0 VDC
Short
0.0 - 1.3 VDC
Point 3 Point 4
Point 5 Point 6
Point 7 Point 8
12
13
14
15
16
17
18
19
20
Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
32
RED
POWER +
31
YELLOW
DATA BUS A
GREEN
DATA BUS B
30
7
29
BLACK
COMMON
N.F.P.A.
28
ZONEX OUT 1
Style 3.5
Signaling
Line
27
Circuits
ZONEX IN 1
26
ZONEX OUT 2
25
ZONEX IN 2
24
ZONEX POWER +
23
ZONEX COMMON
Point 8
PROG
GND FAULT
CONN
Detect
D
E
I
N
S
A
A
B
B
L
21
22
L
GRN
E
E
© 2002 Radionics

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412g

Table of Contents