CONTROL CONNECTIONS

The control connections (analog inputs/outputs, digital inputs/
outputs), must be made at the CC11 control board terminal strip XC1.
XC1
Terminal Strip
CW
1
REF+
2
AI1+
≥5 kΩ
3
AI1-
4
REF-
CCW
5
AI2+
6
AI2-
rpm
7
AO1
AGND
8
(24 V)
amp
9
AO2
AGND
10
(24 V)
11
DGND*
12
COM
13
24 Vdc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NC1
22
C1
23
NO1
24
NC2
25
C2
26
NO2
27
NC3
28
C3
29
NO3
Figure 21: Signals at connector XC1 - digital inputs working as
"Active High"
NOTE!
For changing to "Active Low" remove the jumpers
between XC1:11 and 12, place this jumper between
XC1:12 and 13 and connect common points of the
switches on DI1 to DI6 to XC1:11, instead of XC1:13.
Factory Setting Function
Positive reference for
potentiometer (5.4 V ± 5 %).
Analog input # 1:
Speed reference (remote).
Negative reference for
potentiometer (-4.7 V ± 5 %).
Analog input # 2:
No function.
Analog output # 1:
Speed.
Reference (0 V) for the analog
outputs.
Analog output # 2:
Motor current.
Reference (0 V) for the analog
outputs.
Reference (0 V) for the 24 Vdc
power supply.
Common point of the digital
inputs.
24 Vdc power supply.
Common point of the digital
inputs.
Digital input # 1:
Start / Stop.
Digital input # 2:
Direction of rotation (remote).
Digital input # 3:
No function.
Digital input # 4:
No function.
Digital input # 5:
Jog (remote).
Digital input # 6:
2
nd
ramp.
Digital output #1 DO1 (RL1):
No fault.
Digital output #2 DO2 (RL2):
N > N
- Speed > P0288.
X
Digital output #3 DO3 (RL3):
N* > N
- Speed reference >
X
P0288.
ON
1 2 3 4
1
XC1
29
Factory Default
DIP-
Signal
Function
switch
Speed Reference
OFF: 0 to 10 V (factory setting)
AI1
S1.4
(remote)
ON: 4 to 20 mA / 0 to 20 mA
OFF: 0 to ±10 V (factory setting)
AI2
No Function
S1.3
ON: 4 to 20 mA / 0 to 20 mA
OFF: 4 to 20 mA / 0 to 20 mA
AO1
Speed
S1.1
ON: 0 to 10 V (factory setting)
OFF: 4 to 20 mA / 0 to 20 mA
AO2
Motor Current
S1.2
ON: 0 to 10 V (factory setting)
Figure 22: DIP Switches for setting signal type on analog inputs and
outputs
NOTE!
For information of Safety Stop (STO) function refer
to Installation, Configuration and Operation guide.
Installation Guide