Maximum braking
Inverter model
CFW11 0006 B 2
CFW11 0006 S 2 O FA
CFW11 0007 B 2
CFW11 0007 S 2 O FA
CFW11 0007 T 2
CFW11 0010 S 2
CFW11 0010 T 2
CFW11 0013 T 2
CFW11 0016 T 2
CFW11 0024 T 2
CFW11 0028 T 2
CFW11 0033 T 2
CFW11 0045 T 2
CFW11 0054 T 2
CFW11 0070 T 2
CFW11 0086 T 2
CFW11 0105 T 2
CFW11 0003 T 4
CFW11 0005 T 4
CFW11 0007 T 4
CFW11 0010 T 4
CFW11 0013 T 4
CFW11 0017 T 4
CFW11 0024 T 4
CFW11 0031 T 4
CFW11 0038 T 4
CFW11 0045 T 4
CFW11 0058 T 4
CFW11 0070 T 4
CFW11 0088 T 4
CFW11 0142 T 2 O DB
CFW11 0180 T 2 O DB
CFW11 0211 T 2 O DB
CFW11 0105 T 4 O DB
CFW11 0142 T 4 O DB
CFW11 0180 T 4 O DB
CFW11 0211 T 4 O DB
Notes:
(1) The effective braking current presented is just an indicative value, because it depends on the braking duty cycle. The effective braking current can be obtained from the equation below, where t
is given in minutes and corresponds to the sum of all braking times during the most severe cycle of 5 (five) minutes.
t
I
= I
·
br
effective
max
5
(2) The P
and P
values (maximum and mean power of the braking resistor respectively) presented are valid for the recommended resistors and for the effective braking currents presented in the
max
R
table. The resistor power must be changed according to the braking duty cycle.
Table A.3: Dynamic braking specifications for sizes A to E
Maximum braking
Effective braking
current
power (peak value)
(I
)
(P
)
(2)
max
max
[A]
[kW]
5.3
2.1
5.3
2.1
7.1
2.9
7.1
2.9
5.3
2.1
11.1
4.4
7.1
2.9
11.1
4.4
14.8
5.9
26.7
10.7
26.7
10.7
26.7
10.7
44
17.6
48.8
19.5
48.8
19.5
93
37.2
111.1
44.4
3.6
2.9
5.3
4.3
5.3
4.3
8.8
7
10.7
8.5
12.9
10.3
17
13.6
26.7
21.3
36.4
29.1
47.1
37.6
53.3
42.7
66.7
53.3
87.9
70.3
266.7
106.7
266.7
106.7
333.3
133.3
186
148.8
266.7
213.3
266.7
213.3
363.6
290.9
Dissipated power
Recommended
current
(mean value) in the
(I
)
braking resistor
(1)
effective
[A]
(P
)
[kW]
(2)
R
5.2
2.03
5.2
2.03
6.96
2.71
6.96
2.71
5.2
2.03
10.83
4.22
6.96
2.71
8.54
2.62
14.44
5.63
19.15
5.5
18.21
4.97
16.71
4.19
33.29
10.1
32.17
8.49
26.13
5.6
90.67
35.3
90.87
29.7
3.54
2.76
5.2
4.05
5.2
4.05
8.57
6.68
10.4
8.11
12.58
9.81
16.59
12.9
20.49
12.6
26.06
14.9
40
27.2
31.71
15.1
42.87
22.1
63.08
36.2
142
30.2
180
48.6
211
53.4
105
47.4
142
60.5
180
97.2
191.7
80.8
Installation Guide
Power wire size (terminals
resistor
DC+ and BR)
[Ω]
[mm
2
(AWG)]
75
1.5 (16)
75
1.5 (16)
56
1.5 (16)
56
1.5 (16)
75
1.5 (16)
36
2.5 (14)
56
1.5 (16)
36
2.5 (14)
27
4 (12)
15
6 (10)
15
6 (10)
15
6 (10)
9.1
10 (8)
8.2
10 (8)
8.2
6 (8)
4.3
35 (2)
3.6
35 (2)
220
1.5 (16)
150
1.5 (16)
150
1.5 (16)
91
2.5 (14)
75
2.5 (14)
62
2.5 (12)
47
4 (10)
30
6 (10)
22
6 (8)
17
10 (8)
15
10 (8)
12
10 (6)
9.1
25 (4)
1.5
70 (2/0) or 2x 25 (2x 4)
1.5
120 (4/0) or 2x 35 (2x 2)
1.2
150 (300) or 2x 50 (2x 1)
4.3
50 (1)
3
70 (2/0) or 2x 25 (2x 4)
3
120 (4/0) or 2x 35 (2x 2)
2.2
120 (250) or 2x 50 (2x 1)