Deif CGC 400 Installation Instructions Manual page 9

Compact genset controller
Hide thumbs Also See for CGC 400:
Table of Contents

Advertisement

CGC 400 installation instructions
4189340785 UK
Term
Technical data
3-phase generator voltage input
33
Gen. voltage L1
34
Gen. neutral
35
Not used, must not be connected
36
Gen. voltage L2
37
Not used, must not be connected
38
Gen. voltage L3
3-phase generator current input
39
Gen. current L1, s1
40
Gen. current L1, s2
41
Gen. current L2, s1
42
Gen. current L2, s2
43
Gen. current L3, s1
44
Gen. current L3, s2
3-phase mains voltage inputs
28**
Mains voltage L1
29**
Mains voltage neutral
30**
Mains voltage L2
31**
Not used, must not be connected
32**
Mains voltage L3
Breaker relays
45
Relay R45
46
Relay R45
Optional relay for closing mains breaker
47
Relay R47
48
Relay R47
Modbus RS 485
49
B(-)
50
GND
51
A (+)
CAN bus port: engine interface
53
CAN-H
54
CAN-GND
55
CAN-L
* The status relay is the uP watchdog output. This relay is normally energised, and the switch
is closed after power-up. If the uP fails or the power is lost, the relay will de-energise and the
switch will open. If the unit fails to start up at power-up, then the relay switch will remain open.
DEIF A/S
Description
GENERATOR VOLTAGE
GENERATOR CURRENT
MAINS VOLTAGE
Generator circuit breaker/configurable, function NO (normally
open)
Mains circuit breaker/configurable, function NC (normally
closed)
Modbus RS-485 RTU. Speed is fixed to 9600 bit/s.
The CAN bus interface to J1939. The 120 ohm termination re-
sistor is wired internally. It is not needed to add an external re-
sistor.
Terminals
Page 9 of 25