CGC 400 installation instructions
4189340785 UK
**Terminals are not available in CGC 412.
The relay output functions are configurable via the PC utility software and can be configured to cover the fol-
lowing functions:
Alarm/limit
Engine run indication
Horn
Idle speed output
Not used
Prepare
Run coil
Starter
Stop coil
Engine heater
Fuel pump
It is possible to choose run coil on one relay and stop coil on another, thus supporting engines with double
systems.
The multi-functional inputs can be configured to cover the following functions:
RMI sensor input
Pt100 and Pt1000
4 to 20 mA input
Binary input with wire break (switch function)
Tacho RPM input (MPU) can be configured to cover the following functions:
Magnetic pickup (2-wire)
NPN or PNP pickup (these RPM inputs require external equipment)
Tacho RPM input with capacitor (W/L) can be configured to cover the following functions:
Magnetic pickup (2-wire)
W terminal on charger alternator
NPN or PNP (these RPM inputs require external components)
The generator voltage and current input can be configured to the following:
Voltage 100 to 25000 V primary
Current 5 to 9000 A primary