CGC 400 installation instructions
4189340785 UK
**Terminals are not available in CGC 412.
The relay output functions are configurable via the PC utility software and can be configured to cover the fol-
lowing functions:
●
Alarm/limit
●
Engine run indication
●
Horn
●
Idle speed output
●
Not used
●
Prepare
●
Run coil
●
Starter
●
Stop coil
●
Engine heater
●
Fuel pump
It is possible to choose run coil on one relay and stop coil on another, thus supporting engines with double
systems.
The multi-functional inputs can be configured to cover the following functions:
●
RMI sensor input
●
Pt100 and Pt1000
●
4 to 20 mA input
●
Binary input with wire break (switch function)
Tacho RPM input (MPU) can be configured to cover the following functions:
●
Magnetic pickup (2-wire)
●
NPN or PNP pickup (these RPM inputs require external equipment)
Tacho RPM input with capacitor (W/L) can be configured to cover the following functions:
●
Magnetic pickup (2-wire)
●
W terminal on charger alternator
●
NPN or PNP (these RPM inputs require external components)
The generator voltage and current input can be configured to the following:
●
Voltage 100 to 25000 V primary
●
Current 5 to 9000 A primary
DEIF A/S
Terminals
Page 10 of 25