Quick Start Guide
2.1 Power supply
The dc power supply should provide power with less than two percent ripple. The
total resistance load is the sum of the resistance of the signal leads and the load
resistance of the controller, indicator, and related pieces. Note that the resistance
of intrinsic safety barriers, if used, must be included.
Figure 2. Load Limitation
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 11.25)
1387
1000
500
0
11.25
Voltage (V dc)
The Field Communicator requires a minimum loop resistance of 250Ω for communication.
3.0 Configure the transmitter
Note:
A check (✓) indicates the basic configuration parameters. At a minimum, these parameters should
be verified as part of the configuration and startup procedure.
Table 1. Field Communicator Fast Key Sequence
Function
Alarm Level Config.
Alarm and Saturation Levels
Analog Output Alarm Direction
Analog Output Trim
Burst Mode On/Off
Burst Options
Damping
Date
Descriptor
4
Operating
Region
30
20
42.4
Fast Key sequence
1, 4, 2, 7, 7
1, 4, 2, 7
1, 4, 2, 7, 6
1, 2, 3, 2
1, 4, 3, 3, 3
1, 4, 3, 3, 4
1, 3, 6
1, 3, 4, 1
1, 3, 4, 2