Emerson Rosemount 4600 Quick Start Manual page 3

Oil & gas panel pressure transmitter
Hide thumbs Also See for Rosemount 4600:

Advertisement

September 2016
1.0 Mount the transmitter
1.1 Electrical connection
1. Pull the leads through the threaded mounting hole in the panel wall.
2. Hand tighten the electrical connection into the mounting hole.
3. Using a wrench on the hex flat at the process connection, apply sufficient
torque to prevent transmitter vibration. Do not exceed 100 ft-lbs.
1.2 Process connection
1. Hand tighten the appropriate sized impulse piping connector into the process
connection.
2. Using a wrench on the hex flat at the impulse piping connection, apply
enough torque to prevent process fluid leakage. Do not exceed 100 ft-lbs.
2.0 Connect the wiring and power
Use the following steps to wire the transmitter:
1. Connect the red lead to the "+" terminal of the power supply.
2. Connect the black lead to the "-" terminal of the I/O card on the PLC.
3. Connect the green lead to panel ground.
The figure below shows the wiring connections necessary to power a Rosemount
4600 and enable communications with a hand-held Field Communicator.
Figure 1. Rosemount 4600 Field Wiring
A
A. Rosemount 4600
B. R
> 250 ohm
L
C. Power supply
B
F
D. I/A card
E. PLC
F. Field Communicator
Quick Start Guide
C
D
E
3