Quick Start Guide
7.0 Product Certifications
Rev 1.3
7.1 European directive information
A copy of the EU Declaration of Conformity can be found at the end of the Quick
Start Guide. The most recent revision of the EU Declaration of Conformity can be
found at EmersonProcess.com/Rosemount.
7.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the
design meets the basic electrical, mechanical, and fire protection requirements
by a nationally recognized test laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
North America
E5 US Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 3012302
Standards: FM Class 3600 - 2011; Class 3615 - 2006; FM Class 3810 - 2005;
Markings: Explosionproof for Class I, Division 1, Groups B, C, and D; Flameproof for
I5 US Intrinsic Safety (IS), Nonincendive (NI)
Certificate: 3012302
Standards: FM Class 3600 - 2011; Class 3610 - 2010; Class 3611-2004; NEMA 250 -
Markings: Intrinsically Safe for use in Class I, Division 1, Groups A, B, C, and D;
E6 Canada Explosionproof and Division 2
Certificate: 1384913
Standards: CSA Std C22.2 No. 25-1966; CSA Std C22.2 No. 30-M1986; CAN/CSA-C22.2
Markings: Explosionproof for Class I, Division 1, Groups B, C, and D; Dust-Ignitionproof
10
NEMA 250 - 1991; ANSI/ISA-S12.0.01 - 1998; ANSI/ISA-S12.22.01- 1998;
ANSI/ISA-60079-0 - 2009;
Class 1, Zone 1 AEx d IIC T5 (–40 °C to 85 °C); Dust-ignition proof for Class II
and Class III, Division 1, Groups E, F, and G; Temperature Code T5
(T
= –40 °C to 85 °C); Enclosure Type 4X; Conduit seal not required.
amb
1991; ANSI/ISA-S12.0.01 - 1998; ANSI/ISA-S12.22.01 - 1998;
ANSI/ISA-60079-0-2009; ANSI/ISA-60079-11- 2009
Temperature Code T4 (–50 °C to 70 °C); Intrinsically Safe for use in Class I,
Zone 0 AEx ia IIC T4 (–50 °C to 70 °C) in accordance with control drawing
04620-5007; Nonincendive for Class I, Division 2, Groups A, B, C, and D
when connected in accordance with Rosemount drawing 04620-5007;
Enclosure Type 4X
No. 94-M91; CSA Std C22.2 No. 142-M1987; CAN/CSA-C22.2 No. 157-92;
CSA Std C22.2 No. 213-M1987; CAN/CSA-E79- 0-95; CAN/CSA- E79-1-95;
CAN/CSA- E79-11-95; ANSI/ISA No. 12.27.01-2011
for Class II and Class III, Division 1, Groups E, F, and G; Temperature Code T5
(–50 °C to 40 °C); Explosion-proof for Class 1, Zone 1 Ex d IIC T5 (–20 °C to
40 °C); Suitable for Class I, Division 2, Groups A, B, C, and D when installed
per Rosemount drawing 04620-5005; Enclosure Type 4X; Conduit seal not
required.