The momentary rms voltage is constantly monitored by the Analyzer. It calculates an
average from these measuring values across 10-minute observation periods. The 10-
minute averages are compared against the tolerance range (in this example 102 ... 138 V).
The 100 % limit means that the 10-minute averages must always (i.e. 100 % of time or
with 100 % probability) be within range. The bar graph will turn to red if a 10-minute
average crosses the tolerance range.
The adjustable limit of for instance 95 % (i.e. 95 % probability) means that 95 % of the
10-minute averages must be within tolerance. The 95 % limit is less stringent than the
100 % limit. Therefore the related tolerance range usually is tighter. For 120 V this for
instance can be + or – 10 % (a tolerance range between 108 ... 132 V).
The bars for Dips/Interruptions/Rapid Voltage Changes/Swells are narrow and indicate
the number of limits violations that occurred during the observation period. The allowed
number is adjustable (for instance to 20 Dips/week). The bar turns to red if the adjusted
limit is violated.
You can use a pre-defined set of limits or define your own. The pre-defined set is that
according to the EN50160 standard. You can define your own set of limits and save it in
memory under a user-definable file name. As a basis for this set you can use EN50160 or
any other set. Refer to Chapter 24 Paragraph Limits Adjustments for a description.
The table below gives a survey of the aspects of Power Quality Monitoring:
Parameter
Vrms
Harmonics
Flicker
Dips/Interruptions/Rapid
Voltage Changes/Swells
Unbalance
Frequency
Mains Signaling
info@Fluke-Direct.ca
Available Bar Graphs
3, one for each phase
Probability 100 %: upper
& lower limit
Probability x %: upper &
lower limit
3, one for each phase
Probability 100 %: upper
limit
Probability x %: upper
limit
3, one for each phase
Probability 100 %: upper
limit
Probability x %: upper
limit
4, one for each
allowed number of
parameter covering all 3
events per week
phases
1, covering all 3 phases
Probability 100 %: upper
limit
Probability x %: upper
limit
1, covering all 3 phases
* Probability 100 %:
Measured on Reference
upper & lower limit
Voltage Input A/L1
Probability x %:
upper & lower limit
6, one for each phase,
* Probability 100 %
for freq 1 and freq 2
upper limit: N/A
Probability x %:
upper limit: adjustable
Fluke-Direct
Monitor - Power Quality Monitoring
Limits
Averaging Interval
10 minutes
10 minutes
2 Hrs.
½ cycle rms based
10 minutes
10 sec.
3 sec. rms
.ca
16
Introduction
16-3
1.800.868.7495

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

435-ii437-ii

Table of Contents