Measurement items
Trend
Harmonics
Dips & Swells
Flicker
Phasor
Power
Cycle aggregation
1
When K-factor method is set to US, then K-factor e parameter and the K-factor q parameter are disabled.
info@Fluke-Direct.ca
Table 24-1. Function Preference, Measurement Items Overview
Measurement sub
items
Default duration
Average time
Start Delay
Scale
Interharmonics
THD
K-factor method
1
K-factor e
1
K-factor q
Reference
Lamp model
Clockwise
Method
Display
Interval
Wave Capture (available under Function key F1): parameters can be set
10
here related with capture of voltage and current waveforms in modes
such as Transients and Flicker. In this menu Function key F4 can be
used to reset to Defaults and Function key F5 to leave the menu.
Inrush (available under Function key F2): menu to set the default
11
parameters for the Inrush measurement. In this menu Function key F5
can be used to leave the menu.
Rapid Change (available under Function key F3): menu to set the
12
parameters for the Rapid Voltage Change measurement (Voltage
tolerance, Steady time, Minimum step, Detect on Vstep/Vmax). In this
menu Function key F4 can be used to reset to Defaults and Function
key F5 to leave the menu.
Fluke-Direct
Default setting
7 d
1 s
10 s
% f
OFF
40 harmonics
1
US
0.1
1.7
Nominal
Fnom
neg
Unified
Fnom = 50Hz: Cos Φ
Fnom = 60Hz: DPF
10/12 cycles
400 Hz: 80 cycles fixed
Setting up the Analyzer
MANUAL SETUP
Measurement sub
item values and
ranges
1 hr, 2 hr, 4 hr, 8 hr, 16
hr, 24 hr, 2 d, 7 d, 30 d,
3 mon, 6 mon, 12 mon.
0.25 s, 0.5 s, 1 s, 3 s, 5
s, 10 s, 30 s, 1 m, 5 m,
10 m, 15 m, 30 m , 1 hr,
2 hr.
10 ... 999 s (step: 1s)
% f, % r, rms
ON, OFF
40, 50 harmonics
EU, US
0.00 ... 0.20 (step 0.01)
1.00 ... 2.00 (step 0.01)
Nominal, sliding
50Hz/230V, 60Hz/120V
neg, pos
Classic, Unified
Cos Φ, DPF
10/12 cycles,
150/160 cycles (3s)