System Specifications; System Power Requirements - Acopia ARX 1000 Hardware Installation Manual

Adaptive resourse switch
Table of Contents

Advertisement

Chapter 4

System Specifications

Component
Chassis Dimensions
(includes front bezel)
Weight
Power Load
AC/DC Power Supply
Environmental Requirements
Table 4.1 ARX®1000 System Specifications

System Power Requirements

4 - 4
Table 4.1 describes the ARX®1000 system specifications.
Specification
Height: 3.375 in.
Width: 19.00 in. (including the fixed mounting ears)
Depth: 23.75 in.
35 lb (15.88 kg)
5.7 amps @ 110Vac, 3.1 amps @ 220Vac
450 Watts @ +2.5 V, +3.3 V, and +12.0 V
Note that the power supply draws a total of 608W from the AC power
cord due to its operating efficiency.
Altitude: -200 ft. (-60 m) min. to 8000 ft. (2500 m) max.
Humidity —
Operating: 5 % min. to 95% max. (non condensing)
Storage: 5% to 95%
Temperature —
Operating: 32 deg. to 104 deg. F (0 deg. to 40 deg. C)
Storage: -40 deg. to 149 deg. F (-20 deg. to 65 deg. C)
The ARX®1000 power supply distributes up to 450 Watts of DC power to
the chassis components. The power supply runs at 74% efficiency, so it
consumes up to 608 Watts of AC power (450/0.74) to meet the 450-Watt
demand. This is equivalent to 2,075 BTUs/hour.