2. SPECIFICATIONS
2.1 Enclosure
NEMA 4X.
To prevent any interference from electromagnetic radiation, use rigid metal
conduit to enclose the wiring entering the ER3000. Two 1/2NPT wire ports have
been provided for this purpose. If unused, properly seal with a metal plug.
2.2 Media
The preferred media is clean, dry instrument grade air or nitrogen. Use
of an in-line 40-micron filter is highly recommended to prevent damage
to the solenoid valves.
2.3 Inlet Pressure
Minimum:
Maximum:
Typical:
Note: Response time is affected by input pressure.
2.4 Environment
Temperature:
Pressure:
Humidity:
2.5 Flow Rate
Cv:
Note: The flow rate can be increased using a booster regulator.
2.6 Power Requirement
Voltage:
Current:
2.7 RS485 Communication Interface
Networking:
Cable length:
Baud rate:
8 ER3000 User Manual
Outlet pressure + 1 PSIG.
120 PSIG.
110 PSIG.
-30ºC to 75°C (Dry nitrogen supply gas).
-20ºC to 60ºC (KEMA Explosion Proof Versions M & N)
5ºC to 75°C (Shop air).
28 - 32 inches Hg
To 100% R.H (non-condensing) @ 0°C to 75ºC.
0.01.
24V (22V to 28V)
340mA Max, 180mA Nominal
Up to 32 controllers on one network.
4000 ft. Max.
9600