Tescom ER3000 Manual
Hide thumbs Also See for ER3000:

Advertisement

ER3000
Explosion Proof
Manual
ELECTRONIC CONTROLS DIVISION
www.tescom.com

Advertisement

Table of Contents
loading

Summary of Contents for Tescom ER3000

  • Page 1 ER3000 Explosion Proof Manual ELECTRONIC CONTROLS DIVISION www.tescom.com...
  • Page 2 ER3000 EXPLOSION PROOF MANUAL This manual provides basic installation information and safety precautions for the following Tescom ER3000 Pressure Controllers: MODEL NO. DESCRIPTION ER3000EI-1 4-20 mAmp/1-5 VDC analog setpoint and feedback FM Explosion Proof Packaging (Class I, Division I, Groups B, C, & D) CSA Explosion Proof Packaging (Class I, Groups B, C &...
  • Page 3: Table Of Contents

    Sensor Update Rate ........ER3000 Installation Flow Chart & ER3000 Wiring Diagram ..
  • Page 4: Introduction

    INTRODUCTION The ER3000 Series (Electronic Regulator) is a versatile 0 to 100 PSIG pressure controller. It can be used in conjunction with any pneumatically actuated regulator or valve to control pressure. Setpoints can be provided via an analog input (4-20mA, 1-5V, or 0-10V), the digital RS485 interface, or a downloaded profile.
  • Page 5: Hazardous Locations Certifications

    HAZARDOUS LOCATIONS CERTIFICATIONS Factory Mutual (FM) Approval: Explosion Proof Identification No. 2Z0A0.AE Class I, Division I, Groups B, C, and D Enclosure type 4X SPECIAL CONDITIONS FOR SAFE USE – -20°C ≤ T ≤ 60°C – Do not remove cover while circuits are live –...
  • Page 6: Specifications

    NEMA 4X / IP65. To prevent any interference from electromagnetic radiation, use rigid metal conduit to enclose the wiring entering the ER3000. Two 1/2" NPT wire ports have been provided for this purpose. If unused, properly seal with a metal plug.
  • Page 7: Response Time

    Response Time Rise Time: 257ms. - 10 PSIG to 90 PSIG Fall Time: 552ms. - 90 PSIG to 10 PSIG Note: Step response into dead-end system (1 cubic inch volume). Ports Conduit: 1/2" NPT Pneumatic: 1/8" NPT - Inlet, exhaust and gauge ports 1/4"...
  • Page 8: Er3000 Installation Flow Chart & Er3000 Wiring Diagram

    FLOW CHART WIRING DIAGRAM The following tables give the complete Step 1: Select Voltage/Current wiring layout of the ER3000 wiring Jumper J5 (top board – see below assemblies, which are connected to right for Figure 1) – Select Jumper the J3 and J4 terminal blocks. Refer to...
  • Page 9: Safety, Installation, & Operation Precautions

    SAFETY, INSTALLATION, & OPERATION PRECAUTIONS DO NOT ATTEMPT TO SELECT, INSTALL, USE, OR MAINTAIN THIS CONTROLLER, OR ACCESSORY UNTIL YOU HAVE READ AND FULLY UNDERSTOOD THESE INSTRUCTIONS. BE SURE THIS INFORMATION REACHES THE OPERATOR AND STAYS WITH THE PRODUCT AFTER INSTALLATION. DO NOT PERMIT UNTRAINED PERSONS TO INSTALL, USE, OR MAINTAIN THIS CONTROLLER, OR ACCESSORY.
  • Page 10 Refer to product label (modification specific) for maximum inlet pressures. If this rated pressure cannot be found, contact your local Tescom representative for the rated pressure prior to installation and use. Verify the designed pressure rating of all equipment (e.g., supply lines, fittings, connections, filters, valves, gauges, etc.) in your system.
  • Page 11: Installations

    Do not connect the controller, or accessory if you detect oil, grease, or damaged parts. If the controller, or accessory is damaged, contact your local Tescom representative to have the controller cleaned or repaired. Make sure that the components and materials used in the fluid handling system are compatible with the fluid and have the proper pressure rating.
  • Page 12: Safe Component Selection

    BILLS OF MATERIALS Drawings and parts lists for your product may be obtained by calling the number below. Tescom will provide these by fax or mail. Your local Tescom representative can provide additional assistance. Call (800) 447-1250 or email to ecd@tescom.com for assembly/ installation/wiring drawings &...
  • Page 13 ELECTRONIC CONTROLS DIVISION 12616 Industrial Boulevard Elk River, Minnesota 55330-2491 1-800-447-1204 • (763) 241-3238 • FAX (763) 241-3224 e-mail: ecd@tescom.com • www.tescom.com Form No. 1960 Rev. 7/03 Printed 8/03 Printed in U.S.A.

Table of Contents